beautypg.com

Installing the condensing unit (continued) – Vintage Cellars Platinum MIni Split Tech Manual User Manual

Page 31

background image

www.whisperkool.com | Page 29

Measure Superheat

If superheat is high and bubbles are present, add more refrigerant until it is clear. If superheat is low (around 4-6

degrees Fahrenheit) and bubbles are present in the sight glass, check for liquid refrigerant entering the compressor

as evidenced by cool crankcase below 100- 110 degrees Fahrenheit and low discharge superheat. Adjust TXV setting

in small increments to increase superheat and stop liquid from going to the compressor. Check this before adding

more refrigerant. If the temperature of the air entering the condenser is cold enough to cause the condenser fan to

cycle, block about 60% of the coil to raise the head pressure and allow time for stabilization. Reduce blockage if the

condensing temp is above 115 degrees Fahrenheit. Retain blockage if necessary to maintain stability for performance

test listed in the Split System Warranty Checklist. If the air is cold, below 60 degrees Fahrenheit entering the condenser

and the sight glass is clear; allow the system to run for a while until the cellar cools off, then measure and record data

on the Split System Warranty Checklist.

Confirm the controller is displaying the correct temperature and that the controller is not displaying an alarm. If the

controller is displaying an alarm reference page 33 for corrective action. Confirm that the suction line is completely

insulated, from TXV to compressor. Confirm that the sight glass has no bubbles and the ambient temperature around

the condensing unit is not getting excessively hotter. Confirm that both king valves have been back seated and the

nuts have been installed back on the king service ports.

INSTALLING THE CONDENSING UNIT (continued)