Anchor-jamb-head, Frame installation – Oldcastle BuildingEnvelope 3000 Series Thermal MultiPlane User Manual

Page 42

background image

42






S E R I E S 3 0 0 0 T H E R M A L M U L T I P L A N E I N S T A L L A T I O N M A N U A L

FG-2122 FILLER

CUT 4" LONG

(SOLD IN STOCK LENGTHS)

FRAME INSTALLATION

FG-2188 PVC FILLER

MAY BE USED TO IMPROVE

INSTALLATION OF

PERIMETER SEALS.

(OPTIONAL)

SILL ANCHORS, LOCATE NO MORE

THAN 4" AWAY FROM EACH SIDE

OF MULLION. ADDITIONAL ANCHORS

MAY BE REQUIRED BASED ON PROJECT

STRUCTURAL REQUIREMENTS.

SEE PAGES 44 & 45 FOR PERIMETER

ANCHOR CONDITIONS.

NOTES:

1) WHEN USING OPTIONAL FG-3413 SILL RECEPTOR, SILL ANCHORS ARE NOT REQUIRED.

2) ANCHOR SIZE AND FREQUENCY SHOULD BE DETERMINED BY STRUCTURAL REQUIREMENTS.

3) SILL AND HEAD ANCHORS SHOULD BE LOCATED SO THAT THE ANCHOR IS NOT MORE THAN

4" AWAY FROM EACH SIDE OF MULLION.

4) ASSEMBLY WITHOUT FLASHING IS NOT RECOMMENED.

5) ASSEMBLY USING A NON-THERMAL OR SHEET METAL FLASHING WILL RESULT IN LOSS OF

THERMAL CONTINUITY AND IS NOT RECOMMENDED.

6) DO NOT ANCHOR WALL THROUGH VERTICAL LEG OF SUB-SILL.

SEE PAGE 44 & 45 FOR OPTIONAL HEAD

ANCHORAGE.