Install-fg-3413-subsill, Install sill receptor and end dam – Oldcastle BuildingEnvelope 3000 Series Thermal MultiPlane User Manual
Page 10

FG-3413
ANCHOR SILL RECEPTOR WITHIN 4" FROM EITHER
SIDE OF INTERMEDIATE MULLIONS. ANCHOR
SIZE AND FREQUENCY SHOULD BE
DETERMINED BY STRUCTURAL REQUIREMENTS.
CAP SEAL FLASHING ANCHORS AS SHOWN.
SEAL END DAM TO
SILL RECEPTOR.
INSTALL SILL RECEPTOR AND END DAM
FG-3413
INSTALL SPLICE SLEEVE
NOTE: INSTALL SILL RECEPTOR LEVEL.
FG3000-FP-47
1/4" NOMINAL
SEAL WITH A NON-SKINNING
NON-HARDENING SEALANT.
FILL BREAK IN FLASHING
AND UNDER SPLICE.
FG3000-FP-46
SET FRONT OF FRAME IN
SILL RECEPTOR AND TILT
BACK INTO PLACE.
INSTALLATION INSTRUCTIONS FOR
OPTIONAL FG-3413 SILL RECEPTOR
CLEAN EXCESS
SEALANT AWAY.
INTERIOR PERIMETER SEAL
AT SILL IS OPTIONAL AND FOR
COSMETIC PURPOSES ONLY.
NOTE: IF A TWO PIECE HEAD RECEPTOR
IS NOT USED, A 1/4" MINIMUM CLEARANCE
IS REQUIRED AT THE HEAD CONDITION TO
ALLOW FRAME INSTALLATION.
SEAL SILL RECEPTOR
VERTICAL SPLICE JOINT
JUST PRIOR TO FRAME INSTALLATION,
APPLY CONTINUOUS SEALANT ALONG
GROOVE IN FRONT AND BACK LEGS OF
SILL RECEPTOR AND AROUND JOINT AS
SHOWN. IMMEDIATELY INSTALL FRAME
INTO SILL.
REFERENCE DETAIL "A"
PAGE 9 FOR ADDITIONAL
SEALANT INFORMATION
NOTE:
1) SILL RECEPTOR SHALL BE INSTALLED
LEVEL AND SHOULD NEVER TILT
TOWARDS INTERIOR OF BUILDING.
2) THE FG-3413 SILL RECEPTOR IS DESIGNED
TO WITHSTAND A MAXIMUM END REACTION
OF 600 LBS.
3) SPLICE SILL RECEPTOR AT MID-LITE.
4) LOCATE SPLICE JOINT AT DISTANCE OF NO
MORE THAN EVERY 12 FEET.
DRILL 1/4" WEEP HOLES
LOCATE AT MID-LITE
SHIM UNDER
SILL RECEPTOR.
10
S E R I E S 3 0 0 0 T H E R M A L M U L T I P L A N E I N S T A L L A T I O N M A N U A L