HINGE TEMPLATE FOR
5 KNUCKLE STANDARD
WEIGHT
Door Side
Jamb Side
DOOR PREPARATION:
The wire chase should be drilled through the door with a 3/8" drill bit starting at point noted on the hinge
template.
The Detex hinge should always be positioned as one of the center hinges on the door, since the modified hinge
no longer meets manufacturers load bearing specifications.
A starter hole of 3/4"dia x1-1/2" deep is recommended for positioning the splice of the hinge wire and lock
through wire.
Be careful not to pinch wires between the door and hinge when securing the hinge to the door. This may
cause the hinge to malfunction.
Note: In fire rated conditions be sure to confirm the maximum starter hole diameter and depth with the
appropriate testing agency.
FRAME PREPARATION:
Mark and drill hole to receive the wires from the Detex hinge.
Be careful not to pinch wires between the door and hinge when securing the hinge to the door. This may
cause the hinge to malfunction.
Note: Steel based hinges are for interior use only. Use stainless steel or brass based hinges for exterior
installations.
***Do not allow hinge to dangle from its wires during installation***
BURGLAR ALARM SYSTEMS APPLICATIONS:
The ETH hinges are used to pass low voltage power from a frame hinge jamb to the door to power lock sets,
exit devices and door monitoring devices such as door position switches, request to exit switches, etc.
*Detex does not recommend splicing hinges containing 28AWG wire to any wire heavier than 20AWG.*
103152 Page 2