beautypg.com

Appendix g, Thermostat staging algorithm – Carrier 58MVP User Manual

Page 46

background image

Appendix G

Thermostat Staging Algorithm

Unit Default: Algorithm is initiated with Low Heat for 16 minutes. If call for heat still exists, unit transfers into High Heat until thermostat
is satisfied.

Low Heat run time is calculated based on previous heating cycle.

High Heat on time is not calculated. High Heat is energized 1 of 3 ways and runs until thermostat has been satisfied.

1. After Low Heat has run for 16 minutes and call for heat is still present.

2. When algorithm does its calculation of previous cycle and determines High Heat is necessary.

3. After the amount of calculated Low Heat on time has elapsed and there is still a call for heat present.

The following flowchart shows how the algorithm calculates low heat on times. To use calculations, the amount of time unit ran in Low
Heat (LH) and High Heat (HH) during previous cycle must be known. The algorithm uses these values to decide which stage of heat should
be initiated on next call for heat.

Four examples also follow illustrating what the unit will do on a cold start, coming out of night setback, coming on in low fire, and coming
on in high fire.

EXAMPLE 1:
Furnace ran for 16 minutes in Low Heat and 5 minutes in High Heat.
LH = 16
HH = 5
Calculate: (228 X 16) + (350 X 5) = 5398

3648

5398

5600

therefore calculate next cycle Low Heat run time.

LH

run time

=

5600

5398

122

= 1.6

therefore during next cycle, unit will run for 2 minutes in Low Heat and then switch to High

Heat if a call for heat is still present.

EXAMPLE 2:
Furnace ran for 16 minutes in Low Heat and 10 minutes in High Heat.
LH = 16
HH = 10
Calculate: (228 X 16) + (350 X 10) = 7148

7148

5600

therefore next cycle will be initiated in High Heat. Low Heat run time is 0 minutes.

EXAMPLE 3:
Furnace ran for 13 minutes in Low Heat (LH) and 5 minutes in High Heat (HH). This will happen if control algorithm calculated
maximum Low Heat run time be 13 minutes based on a previous cycle.
LH = 13
HH = 5
Calculate: (228 X 13) + (350 X 5) = 4714

3648

4714

5600

therefore calculate the next cycle Low Heat run time.

LH

run time

=

5600

4714

122

= 7.26

therefore unit will run for 7 minutes in Low Heat and then switch to High Heat if a call for

heat is still present.

EXAMPLE 4:
Furnace ran for 0 minutes in Low Heat and 10 minutes in High Heat.
LH = 0
HH = 10
Calculate: (228 X 0) + (350 X 10) = 3500

3500

3648

therefore next cycle will be initiated in Low Heat up to 16 minutes maximum, then switch to High Heat if a call

for heat is still present.

46