Carrier 58MVP User Manual
Page 31
4.
Observe operation of furnace for several minutes or until fault occurs.
—
—
5
5.
Does fault occur again?
9
6
—
6.
Does a different fault occur?
7
8
—
7.
Go to page number indicated in Index for fault code flashed.
—
—
INDEX
8.
Go to page number indicated in Index for CLEANUP AND START-UP INSTRUCTIONS.
—
—
INDEX
9.
Is collector box and inducer housing properly draining condensate?
11
25
—
10.
Fix problem.
—
—
8
11.
Are pressure switches wired correctly?
13
10
—
12.
Replace pressure switch assembly.
—
—
8
13.
Do you have 24v between C (Common) on low-pressure switch LPS and Com on furnace control
board?
15
14
—
14.
The YELLOW wire to low-pressure switch LPS is not making good connection. Repair wire or re-
place harness.
—
—
8
15.
Turn power off and disconnect jumper wire across R, W/W1, and W2 thermostat terminals. Turn
power on and wait a few sec for self test, then reconnect jumper across R, W/W1, and W2 thermo-
stat terminals.
—
—
16
16.
Do you have 24v between connector terminal PL2-2 and Com on furnace control board when fault
occurs?
21
18
—
17.
Replace furnace control board.
—
—
8
18.
Turn power off.
—
—
19
19.
Do you have continuity across terminal PL2-2 and N.O. (Normally Open) contact on low-pressure
switch LPS?
12
20
—
→
20.
The ORANGE wire from low-pressure switch LPS to furnace control board is not making good con-
nection or low gas pressure switch LGPS (when used) is open. Check propane line pressure if us-
ing LGPS otherwise repair wire or replace harness.
—
—
10
21.
Turn power off and disconnect jumper wire across R, W/W1, and W2 thermostat terminals. Discon-
nect BROWN wire from N.O. (Normally Open) contact on high-pressure switch HPS. Turn power on
and wait a few sec for self test, then reconnect jumper across R and W/W1 thermostat terminals.
—
—
22
22.
Does a Fault Code 32 occur?
17
23
—
23.
Reconnect BROWN wire to N.O. (Normally Open) contact on high-pressure switch HPS.
—
—
24
24.
The problem may be caused by a sag in vent pipe. If this is not the problem and fault still occurs,
replace pressure switch assembly.
—
—
8
25.
The vent tube to drain trap, drain trap, or drain line is clogged.
—
—
10
31