beautypg.com

Carrier 58MVP User Manual

Page 43

background image

Tools Needed:

1)

Pitot Tube

1)

Incline Manometer/Magnahelic

Both examples are correct. Example 1 ESP readings were taken as
laid out in Static Pressure Reading Location Diagrams. Example 2
readings are taken as described. The coil and filter static pressure
drops were taken from the manufacturer’s Product Data Sheets
with the assumption that we are trying to deliver 2000 CFM (this
will vary).

NOTE:

By plotting total ESP of 0.95 in. wc on the air delivery

curve of a 100,000 Btuh input furnace, a Fault Code 44 would
flash. (See Example Air Delivery Curve.)

Horizontal Right and Left Airflow Total Static Pressure Reading Locations

A95092

Attic — Horizontal Application

COMBUSTION–AIR PIPE

ELECTRONIC

AIR CLEANER

FURNACE

CONDENSATE

DRAIN

REFRIGERATION

PIPING

AIR CONDITIONING

COIL

AIRFLOW

VENT PIPE

SUPPLY STATIC

INCLINE MANOMETER

RETURN STATIC

INCLINE MANOMETER

Example 1

Return ESP after filter

0.40 in. wc

Supply ESP before coil

0.55 in. wc

Total ESP

0.95 in. wc

Example 2

Return ESP before filter

0.15 in. wc

Filter Static Drop @ 2000 CFM

0.25 in. wc

Supply ESP after coil

0.30 in. wc

Coil Static Drop Wet

0.25 in. wc

Total ESP

0.95 in. wc

43