Carrier 58MVP User Manual
Page 16
16.
Does the installation have a bypass humidifier?
17
30
—
17.
Is setup switch SW-3 in ON position?
19
18
—
18.
Put setup switch SW-3 in ON position.
—
—
9
19.
Cycle furnace with blower access panel in place and record temperature rise across furnace 6 min-
utes after main burner ignition.
—
—
20
20.
Disconnect jumper wire across R and W/W1 thermostat terminals and wait until blower stops.
—
—
21
21.
Remove blower access panel and put setup switch SW-3 in OFF position.
—
—
22
22.
Cycle furnace with blower access panel in place and record temperature rise across furnace 6 min-
utes after main burner ignition.
—
—
23
23.
Is the temperature rise in Step 22 more than 10°F higher than the temperature rise in Step 19?
24
8
—
24.
Disconnect jumper wire across R and W/W1 thermostat terminals and wait until blower stops.
—
—
25
25.
Remove blower access panel and put setup switch SW-3 in ON position.
—
—
26
26.
Cycle furnace with blower access panel in place and record the temperature rise across return air
duct before and after the bypass.
—
—
27
27.
Is temperature rise from bypass greater than 15°F?
28
29
—
28.
The bypass is oversized. Adjust damper or replace with properly sized bypass.
—
—
9
29.
Disconnect jumper wire across R and W/W1 thermostat terminals and wait until blower stops.
—
—
30
30.
Does the installation have modulating zone dampers?
31
51
—
31.
Is setup switch SW-5 in ON position?
33
32
—
32.
Put setup switch SW-5 in ON position?
—
—
9
33.
Jumper R and W/W1 thermostat terminals on furnace control board.
—
—
34
34.
Does blower recalibrate every minute? Check by monitoring DC voltage across terminals PL3-1
RED (+) and PL3-5 BLUE (-). If DC voltage momentarily goes down to 0 vdc approximately every
60 sec after first blower calibration, then blower is recalibating properly.
35
8
—
35.
Disable modulating zone damper system with all dampers in open position except bypass damper.
If the installation is equipped with a bypass damper, it should be in the closed position.
—
—
36
36.
Put setup switch SW-2 in OFF position. Disconnect jumper wire across R and W/W1 thermostat ter-
minals and reset the power. Reconnect jumper wire across R and W/W1 thermostat terminals and
monitor manifold gas pressure while observing furnace operation for 10 minutes.
NOTE:
Blower access panel must be in place.
—
—
37
37.
Does a Fault Code 33 flash?
39
38
—
38.
The problem is cause by the modulating zone damper system. Install a 2-stage thermostat and let
the zone system modulate gas flow. If you still have a problem, check the zone manufacturer’s in-
stallation and Troubleshooting Guide for corrective action.
—
—
9
39.
While monitoring manifold pressure in Step 36, did it drop to low-fire manifold pressure during low-
fire operation?
49
40
—
40.
Replace gas valve.
—
—
9
41.
Replace blower motor and belly band.
NOTE:
Torque belly band screw to 80 in.lb (6.7 ft. lb).
WARNING: DO NOT OVERTIGHTEN!
—
—
9
42.
Jumper R, W/W1, and W2 thermostat terminals on furnace control board.
—
—
43
43.
Is furnace considerably overfired (10% or more)? Clock input rate. Do not use manifold pressure
method unless using propane.
44
45
—
44.
Ensure gas inlet pressure and burner orifices (natural or propane) are correct. Then adjust gas
valve to proper rate per the Installation, Start-Up, and Operating Instructions. If it cannot be ad-
justed to proper rate, replace gas valve.
—
—
9
45.
Disconnect jumper wire across R, W/W1, and W2 thermostat terminals and wait until blower stops.
—
—
6
46.
Excessive restriction of airflow during locked in high-fire mode caused lockout.
—
—
47
47.
Relieve restriction. Check all dampers, filters, and return-air grilles for blockage. Put setup switch
SW-1 in OFF position.
—
—
42
48.
Fix problem.
—
—
9
49.
Is temperature rise within
±
10°F of midpoint of rise range?
51
41
—
50.
Is temperature rise within
±
10°F of midpoint of rise range?
51
16
—
51.
Turn power off and install a temperature probe in front of limit switch button.
—
—
52
52.
Turn power on and cycle unit. Does limit switch open at a temperature at least 10°F below tempera-
ture setpoint for limit switch. (EXAMPLE: The setpoint is 220°F, but switch opens at a temperature
below 210°F.)
7
53
—
53.
The problem may be related ot poor air distribution. Add turning varies, more supply-air openings,
or more return-air openings. Use Appendix E to evaluate.
—
—
48
16