beautypg.com

Fault code 22, Fault code 23 – Carrier 58MVP User Manual

Page 18

background image

Fault Code 22

SETUP ERROR—This fault indicates that setup switches SW-1 or SW-6 are ON when they should be OFF. The
following combinations will cause the fault:

Thermostat call with SW-1 ON.

Thermostat call with SW-6 ON.

SW-1 and SW-6 both ON together.

STEP

ACTION

YES

NO

GO TO

1.

Turn power off and remove blower access panel.

2

2.

Make sure thermostat is NOT calling for heating or cooling. Disconnect all thermostat terminal leads
to make sure.

3

3.

Is setup switch SW-1 in ON position?

4

6

4.

Put setup switch SW-1 in OFF position.

5

5.

Go to page number indicated in Index for CLEANUP AND START-UP INSTRUCTIONS.

INDEX

6.

Is setup switch SW-6 in ON position?

7

8

7.

Put setup switch SW-6 in OFF position.

5

8.

Replace furnace control board.

5

Fault Code 23

INVALID BLOWER AIRFLOW SELECTION—This fault indicates improper A/C or CF switch setting. The -14
units can deliver sufficient airflow for 1-1/2 to 3-1/2 tons A/C and 600 to 1400 CFM for continuous fan. The -20
unit can deliver sufficient airflow for 2 to 5 tons A/C and 800 to 2000 CFM for continuous fan. If fault code is
flashing, unit still operates, but it defaults to closest allowable airflow.

NOTE:

Boards with date codes of 9506 or later will flash fault code and set continuous fan airflow to same airflow as A/C if continuous fan

is adjusted to a higher airflow than A/C setting.

STEP

ACTION

YES

NO

GO TO

1.

Turn power off and remove blower access panel.

2

2.

Are air conditioning select switches A/C set properly? (See Table 2.)

5

3

3.

Set air conditioning select switches A/C for proper tonnage as required by condensing unit.

4

4.

Go to page number indicated in Index for CLEANUP AND START-UP INSTRUCTIONS.

INDEX

5.

Are continuous fan select switches CF set properly? (See Table 3.)

7

6

6.

Set continuous fan select switches CF for desired airflow. This setting should normally be set to DE-
FAULT position unless a 2-speed AC/HP is part of system. Use Table 4 for reference on 2-speed
AC/HP airflow requirements.

4

7.

Are continuous fan select switches CF set to a higher airflow than air conditioning select switches
A/C? (See Tables 2 and 3.)

6

8

8.

Is furnace a 100 size?

11

9

9.

The problem is in the A/C or CF selection circuit. The maximum cooling or continuous fan airflow for
this unit will be delivered.

10

10.

Jiggle A/C and CF switches back and forth. If fault code continues to flash, replace furnace control
board.

4

11.

The problem is in the A/C or CF selection circuit. The minimum cooling or continuous fan airflow for
this unit will be delivered.

12

12.

Jiggle A/C and CF switches back and forth. If fault code continues to flash, replace furnace control
board.

4

18