Carrier 58MVP User Manual
Page 22
25.
Connect 1 side of a slope manometer with a tee to collector box pressure tap. Connect other side
with a tee to gas valve air pressure fitting. Refer to pressure check diagram in Appendix C.
—
—
26
26.
Turn power on and wait several sec, then jumper R and W/W1 thermostat terminals on furnace con-
trol board.
—
—
27
27.
Monitor slope manometer. Does pressure reading appear to be stable when fault occurs?
14
28
—
28.
Check for a sag in vent pipe. If problem persists, replace inducer motor.
—
—
8
29.
Disconnect jumper wire across R and W/W1 thermostat terminals and wait until blower stops.
—
—
30
30.
Jumper R, W/W1, and W2 thermostat terminals on furnace control board.
—
—
31
31.
Does high-pressure switch HPS make, then break several times at start of cycle before faulting out?
32
33
—
32.
The problem is either a sag in vent pipe or a clogged drain trap or line.
—
—
17
33.
Does fault occur before main burners ignite?
34
51
—
34.
Do you have 24v between C (Common) on high-pressure switch HPS and Com on furnace control
board?
36
35
—
35.
The YELLOW wire to high-pressure switch HPS is not making good connection. Repair or replace
it.
—
—
8
36.
Do you have at least 1.90 in. wc pressure drop across heat exchangers when fault occurs? Deter-
mine this by connecting 1 side of slope manometer with a tee to collector box pressure tap. Con-
nect other side with a tee to gas valve air pressure fitting. Refer to pressure check diagram in Ap-
pendix C.
45
37
—
37.
Is inducer motor MTR1 rotating in direction indicated on inducer housing?
39
38
—
38.
Replace inducer motor or inducer motor assembly.
—
—
8
39.
Turn power off.
—
—
40
40.
Is inducer wheel okay?
42
41
—
41.
If possible, replace inducer wheel. Otherwise, replace inducer motor assembly.
—
—
8
42.
Is there any frost build-up on combustion-air inlet?
43
44
—
43.
The problem is caused by reversed vent and combustion-air pipes or some other moist air entering
combustion-air pipe.
—
—
17
44.
You have excessive restriction in combustion-air or vent pipe.
—
—
8
45.
Turn power off and disconnect jumper wire across R, W/W1, and W2 thermostat terminals.
—
—
46
46.
Turn power on and wait several sec, then jumper R, W/W1, and W2 thermostat terminals on fur-
nace control board.
—
—
47
47.
Do you have 24v between connector terminal PL2-4 and Com on furnace control board when fault
occurs?
11
48
—
48.
Turn power off.
—
—
49
49.
Do you have continuity across terminal PL2-4 and N.O. (Normally Open) contact on high-pressure
switch HPS?
14
50
—
50.
The BROWN wire from high-pressure switch HPS to furnace control board is not making good con-
nection. Repair wire or replace harness.
—
—
8
51.
Turn power off and disconnect jumper wire across R, W/W1, and W2 thermostat terminals.
—
—
52
52.
Connect 1 side of a slope manometer with a tee to collector box pressure tap. Connect other side
with a tee to gas valve air pressure fitting. Refer to pressure check diagram in Appendix C.
—
—
53
53.
Turn power on and wait several sec, then jumper R, W/W1, and W2 thermostat terminals on fur-
nace control board.
—
—
54
54.
Monitor slope manometer. Does pressure reading appear to be stable when fault occurs?
55
56
—
55.
Replace pressure switch assembly. If problem persists, check wiring for an intermittent connection
in high-pressure switch HPS circuit.
—
—
8
56.
Check for a sag in vent pipe. If problem persists, replace inducer motor.
—
—
8
22