Carrier 58MVP User Manual
Page 20
18.
Do you have continuity between the N.O. (Normally Open) contact on low-pressure switch LPS and
chassis ground?
19
3
—
19.
The ORANGE wire from low-pressure switch LPS is shorting to ground. Replace or repair it.
—
—
9
20.
Does Fault Code 24 occur when gas valve GV is energized?
21
28
—
21.
Disconnect jumper wire across R and W/W1 thermostat terminals and replace secondary voltage
fuse.
—
—
22
22.
Disconnect BLUE wire to gas valve GV and jumper R and W/W1 thermostat terminals on furnace
control board.
—
—
23
23.
Does Fault Code 34 IGNITION PROVING FAULT occur? If not, Fault Code 24 should occur when
BLUE wire is energized.
27
24
—
24.
Disconnect PL1 from furnace control board.
—
—
25
25.
Do you have continuity between BLUE wire and chassis ground?
26
3
—
26.
The BLUE wire to gas valve GV is shorting to ground. Replace or repair it.
—
—
9
27.
Replace gas valve GV.
—
—
4
28.
Add a jumper across R and W2 thermostat terminals on furnace control board.
—
—
29
29.
Does Fault Code 24 occur when high-pressure switch HPS is energized?
30
39
—
30.
Disconnect jumper wire across R, W/W1, and W2 thermostat terminals and replace secondary volt-
age fuse.
—
—
31
31.
Disconnect BROWN wire to gas valve GV and jumper R, W/W1, and W2 thermostat terminals on
furnace control board.
—
—
32
32.
Does Fault Code 24 occur when high-pressure switch HPS is energized?
33
27
—
33.
Disconnect PL1 from furnace control board.
—
—
34
34.
Do you have continuity between BROWN wire and chassis ground?
35
36
—
35.
The BROWN wire to gas valve GV is shorting to ground. Replace or repair it.
—
—
9
36.
Disconnect PL2 from furnace control board.
—
—
37
37.
Do you have continuity between the N.O. (Normally Open) contact on high-pressure switch HPS
and chassis ground?
38
3
—
38.
The BROWN wire from high-pressure switch HPS is shorting to ground. Replace or repair it.
—
—
9
39.
Disconnect jumper wire across R, W/W1, and W2 thermostat terminals and wait until blower stops.
—
—
40
40.
Jumper R, G, and Y/Y2 thermostat terminals on furnace control board.
—
—
41
41.
Does Fault Code 24 occur when G and Y/Y2 are energized?
3
42
—
42.
Reconnect all thermostat leads (except HUM terminal if used) to furnace control board and operate
furnace in heating and cooling mode from thermostat.
—
—
43
43.
Does Fault Code 24 occur during heating cycle?
44
45
—
44.
You have a defective thermostat or a short circuit in wiring between thermostat and furnace.
—
—
9
45.
Does Fault Code 24 occur during cooling cycle?
46
47
—
46.
You have a defective thermostat or a short circuit in wiring between thermostat and outdoor unit.
—
—
9
47.
Does problem usually occur in cooling mode?
48
49
—
48.
Check outdoor unit contactor. Failure to pull in can cause excessive current draw on low-voltage
circuit. This can be an intermittent problem.
—
—
9
49.
Reconnect humidifier and check for excessive current draw.
—
—
9
20