• Supply may enter heater back box from wall through back

knockout or through top knockout when surface type con-
duit is provided. When surface conduit system is used, the
“U” shaped knockout in the surface frame must be removed
to allow clearance over conduit.

a. Remove the disconnect switch bracket from back box by

removing the two screws.

b. Remove desired knockout in rear or top of back box and run

supply cable to heater location and into upper right corner of
back box, leaving at least 6” of wire inside box for connection.
Cable arrangement must be in accordance with the National
and Local Electric Codes and cable must be properly protect-
ed by use of appropriate cable clamp or conduit fittings.

c. Referring to the appropriate wiring diagram make the follow-

ing connections:
1. Connect the supply ground conductor to the back box by

attaching to the grounding lug marked “Ground.”

2. Connect each supply power lead wire to one of the blue

lead wires from the disconnect switch using wire nuts or
approved wire connectors.

3. If black leads from disconnect switch are not already

attached to terminal block attach as shown in the wiring
diagram. Check to make sure connections are tight.

4. Secure disconnect switch and bracket to back box with the

screws removed earlier.

3. Carefully fit surface frame over back box making sure back
edges of frame are flush with finished wall. See fig. 3. Secure
frame in place with two screws as shown.

Installation of Heater Assembly and Grille

After back box is completely installed and no further construction
dirt is expected, clean debris from back box. Heater fan panels
were shipped mounted to back box and were removed to mount
back box.
1. Insert the heater assemblies (fan panels) into back box, plac-

ing the four mounting holes (with key-hole slots) over the
screws in the back box. Tighten all screws securely.

2. If surface-mounting frame is used, ensure that the

frame is even with all four heater assembly tabs before
tightening screws.

3. Connect the two disconnected black switch wires to the

heater terminal block (see wiring diagram). Connect red, blue
and black wires from both fan panels to heater terminal
block (see

wiring diagram). Check that all wiring connec-

tions are tight.

4. Turn thermostat(s) to the extreme counterclockwise position.
5. Turn disconnect switch “ON”.
6. Mount the grille using the six (6) long screws provided.

The screws thread into holes located in the flanges of the
back box.

Operation

NOTE: The operation instructions apply to 208, 240 and 277V
heaters with one thermostat. Units operating at 347V, 480V and
600V have two thermostats.

3-13/16" (97mm)

HANG FRAME

ON BACK BOX

MOUNT BACK
BOX TO WALL

USING REAR

MOUNTING
BRACKETS

23-7/64" (585mm)

32-7/32" (818mm)

Fig. 3: Surface Mounting Installation

3

L2F

L1

L2E

BLACK

RED

BLUE

BLACK

RED

BLUE

BLACK

L2F

R

E

D

L

2

BLUE

L2E/B

BLACK

L2F

RED

L

1

BLUE

L2E/A

L2F

L1

L2E

Left fan panel
assembly

Right fan panel
assembly

Right fan panel
assembly

To

Disconnect

Switch

Assembly

L2F

L1

L2E/A

L2E/B

L2F

L1

L2E

BLACK

RED

BLUE

BLACK

RED

BLUE

L2F

BLACK

L2

RED

L2E/B

BLUE

BLACK

L2F

RED

L

1

BLUE

L2E/A

L2F

L1

L2E

Left fan panel
assembly

To

Disconnect

Switch

Assembly

L2F

L1

L2E/A

L2E/B

Thermostat

Wiring diagram for
fan panels used on
208V, 240V, 277V
Q Series

Q6008
Q6004
Q6007
Q8008
Q8004
Q6007

Wiring diagram
for fan panels
used on 347V,
480V, 600V
Q Series

Q6003
Q60048
Q6006
Q8003
Q80048
Q8006

Typical Fan Panel Assembly

Typical Fan
Panel Assembly

Terminal Block

Terminal Block