Table 1E — 40RMQ Physical Data, SI — Heat Pump Units
LEGEND
*Units are shipped without refrigerant charge.
UNIT 40RMQ
008
012
016
024
028
NOMINAL CAPACITY (kW)
26
35
52
70
87
OPERATING WEIGHT (kg)
Base Unit with TXV
175
194
323
326
477
Plenum
80
80
102
44
44
FANS
Qty...Diam. (mm)
1...381
1...381
2...381
2...381
2...457
Nominal Airflow (L/s)
1604
1888
2831
3775
4719
Airflow Range (L/s)
1203-2006
1416-2360
2124-3539
2831-4719
3539-5899
Nominal Motor kW (Standard Motor)
208/230-1-60
1.79
—
—
—
—
208/230-3-60 and 460-3-60
1.79
1.79
2.76
3.73
5.60
575-3-60
1.49
1.49
2.24
3.73
5.60
230-3-50, 400-3-50
1.79
2.16
2.16
3.73
5.60
Motor Speed (r/s)
208/230-1-60
28.8
—
—
—
—
208/230-3-60 and 460-3-60
28.8
28.8
28.8
29.1
29.1
575-3-60
28.8
28.8
28.8
29.1
29.3
230-3-50, 400-3-50
23.8
23.8
23.8
23.8
23.8
REFRIGERANT
R-22
Operating charge (kg)
(approx per circuit)*
1.36
0.91/0.91
1.36/1.36
1.59/1.59
2.04/2.04
DIRECT-EXPANSION COIL
Enhanced Copper Tubes, Aluminum Sine-Wave Fins
Max Working Pressure (kPag)
2999
Face Area (sq m)
0.77
0.93
1.85
1.85
2.30
No. of Splits
1
2
2
2
2
No. of Circuits per Split
15
9
18
18
24/16
Split Type...Percentage
—
Face...50/50
Face...60/40
Rows...Fins/m
3...591
4...591
4...591
4...591
4...591
STEAM COIL
Max Working Pressure (kPag at 126 C)
138
Total Face Area (sq m)
0.62
0.62
1.24
1.24
1.39
Rows...Fins/m
1...355
1...355
1...394
1...394
1...394
HOT WATER COIL
Max Working Pressure (kPag)
1034
Total Face Area (sq m)
0.62
0.62
1.24
1.24
1.39
Rows...Fins/m
2...335
2...335
2...335
2...335
2...493
Water Volume
(L)
31.4
52.6
(m
3
)
0.031
0.052
PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil — Vapor (ODF)
1...1
1
/
8
2...1
1
/
8
2...1
1
/
8
2...1
3
/
8
DX Coil — Liquid Refrigerant (ODF)
1...
5
/
8
2...
5
/
8
2...
5
/
8
Steam Coil, In (MPT)
1...2
1
/
2
1...2
1
/
2
1...2
1
/
2
Steam Coil, Out (MPT)
1...1
1
/
2
1...1
1
/
2
1...1
1
/
2
Hot Water Coil, In (MPT)
1...1
1
/
2
1...1
1
/
2
1...2
Hot Water Coil, Out (MPT)
1...1
1
/
2
1...1
1
/
2
1...2
Condensate (Male PVC)
1...1
1
/
4
ODM/1 IDF
FILTERS
Throwaway — Factory Supplied
Quantity...Size
4...406 x 610 x 51
4...406 x 508 x 51
4...406 x 610 x 51
4...406 x 610 x 51
4...406 x 508 x 51
4...406 x 610 x 51
4...508 x 635 x 51
Access Location
Either Side
Right or Left Side
DX
—
Direct Expansion
TXV —