Installation

|

The following table lists backfeed protection devices (AC contactors) that can be used as an external

isolating device for backfeed protection. Only use AC contactors listed in the table.

Table 1. Backfeed Protection Devices

Manufacturer

Type

Rating

ABB France (E12527)

A75-30

220–240 Vac, 105A

25 HP at 208V, 30HP at

240V

Tianshui 213 Electrical Apparatus Co., Ltd.

(E203071)

(alternative)

GSC1(CJX4-d)-6511

220–240 Vac, 68A

25 HP

Tianshui 213 Electrical Apparatus Co., Ltd.

(E203071)

(alternative)

GSC1(CJX4-d)-8011

220–240 Vac, 80A

30 HP

NOTE:

Although the UPS does not contain anti-backfeed (ABF) relays, some backfeed protection is provided.

For example, if some components are damaged in battery mode, the output voltage may feed back to the input.
In this case, a current transformer (CT) is used to detect the bypass current feedback voltage. If a current
backfeed fault condition is detected, the UPS will terminate the inverter output to avoid the personal injury.

6

Connect the input and ground wires to the terminal block according to Figure 22 and Table 2.

1

2

3

Figure 22. Connecting Terminal Block Wiring