Monitor the sensors – Cisco SFS 7008 User Manual
Page 87
87
Note the Speed field. The integer in this field represents a percentage. The percentage changes based on
the ambient temperature of the unit, and will increase as the temperature rises.
Example
Monitor the Sensors
•
show sensor
Example
Note the Temperature field. The temperature is displayed in Celsius. The system’s maximum
external ambient temperature is 30 degrees C (0 – 10,000 ft). Acceptable internal temperature
ranges are 30 degrees C above external ambient, plus 1 degree for every 1,000 ft above sea-level.
The acceptable temperatures for the Topspin 270 varies depending on the card that is being
monitored.
Topspin-270> show fan
================================================================================
Fan Information
================================================================================
fan oper-status speed(%)
--------------------------------------------------------------------------------
1 up 76
2 up 77
3 up 74
4 up 77
================================================================================
Fan Seeprom
================================================================================
product pca pca fru
fan serial-number serial-number number number
--------------------------------------------------------------------------------
1 - - - -
2 - - - -
3 - - - -
4 - - - -
Topspin-270# show sensor
================================================================================
Sensor Information
================================================================================
sensor oper-status oper-code temperature(c) alarm-temp(c) shutdown-temp(c)
--------------------------------------------------------------------------------
10/1 up normal 35 75 85
11/1 up normal 31 75 85
12/1 up normal 29 75 85
13/1 up normal 31 75 85
15/1 up normal 38 70 80
16/1 up normal 37 70 80