8 object 0x6001 units per revolution, 10 object 0x6003 preset value, Object 0x6001 units per revolution – Baumer ATD User Manual

Page 16: Object 0x6003 preset value, Able, 16 p, Roduct specific maxima, Nits per, Evolution value

background image

EtherCAT

16/42

Baumer Thalheim GmbH & Co. KG

2011-10-04/rnik

Eschwege, Germany

This object data will be stored non-volatile after any change. This register may only be changed in case of
ECAT state PREOP or SAFEOP.

2.4.1.8 Object 0x6001 Units per Revolution

This object indicates the number of distinguishable steps per revolution.
The 0x6001 object is a RW register that may be changed if sfc is enabled. The default value gives the En-
coder single turn resolution (e.g. 2

15

= 0x8000).

Resolutions of:

2

n

with n = n

ST

8 < n

ST

< Product Code specific resolution

Value ranges are

Product Code

Encoder Type

Units per Revolution

0x0001 0001

ATD4B***Y***15/16ECM12

0x0000 8000

0x0001 0002

ATD4B***Y***17ECM12

0x0008 0000

0x0002 0001

ATD2B***Y***14/16ECM12

0x0000 4000

0x0002 0002

ATD2B***Y***17ECM12

0x0008 0000

Table 16 Product specific maxima Units per Revolution value

This object data will be stored non-volatile into the encoder memory immediately after any change. This reg-
ister may only be changed in case of ECAT state PREOP or SAFEOP.

2.4.1.9 Object 0x6002 Total measuring range in measuring units

6

This object indicates the number of distinguishable steps over the total measuring range.
The 0x6002 object is a RW register that may be changed if sfc is enabled. The default value gives the En-
coder maxima single turn resolution (e.g. 2

15

= 0x8000) plus a multi turn maxima resolution (e.g. 2

16

-1 =

0xFFFF).Reducing this value always removes multi turn resolution bits keeping the single turn at it maxima
the value set up under object 0x6001. This register may only be changed in case of ECAT state PREOP or
SAFEOP.

Total measuring range in measuring units is:

2

n

with n = n

MT

(8 + n

ST

) < n

MT

< (16 + n

ST

)

The total measuring range can be calculated by the following formula:

= Single turn resolution (0x6001) x Number of distinguishable revolutions (0x6502)
= n

ST

+ n

MT

In case of an ST this Object is a mirror of the 0x6001 Object.
This object data will be stored non-volatile into the encoder.

2.4.1.10 Object 0x6003 Preset Value

This object indicates the preset value for the output position value. The 0x6003 object is a RW register in
case of ECAT state PREOP or SAFEOP, this means in OP state changes are not allowed. The device quits
changes during OP state with the SDO message “Abort ('Attempt to write a read only object', 0x06010002)”.

This object data shows a volatile (non back up) data default value is 0x00000000, true encoder offset value
is given by Object 0x6509.

6

For Multi Turn devices only