5 technical data – Baumer TA1200 User Manual
Page 23
![background image](/manuals/604465/23/background.png)
TA1200
www.baumer.com
23
5 Technical data
Technical data - electrical ratings
Voltage supply
21...53 VAC (50/60 Hz) or
10.5...70 VDC
85...265 VAC (50/60 Hz) or
100...300 VDC
Power consumption
2.2 W
Sensor supply
5 V, 8 V or 12 V
programmable/60 mA
Display
LED, 7-segment display (with 60 unit
stickers for front)
Number of digits
4-digits
Digit height
10 mm
Display range
9999 („OuE“ to signal overflow)
Display refresh
0.1... 9.9 s (programmable)
Programmable
Measuring units 1/h, 1/min, 1/s
parameters
Sensor logic
Decimal point
Sensor supply
Impulse evaluation
Measuring principle
Period duration measurement
Signal inputs
Programmable as NPN, PNP, Namur,
TTL, 10...600 VAC or contact
Counting frequency
0.01 Hz...7 kHz (20 Hz if contact input)
Data memory
>10 Jahre in EEPROM
Standard
Protection class II
DIN EN 61010-1
Overvoltage category II
Pollution degree 2
Emitted interference
DIN EN 61000-6-3
Interference immunity
DIN EN 61000-6-2
Technical data - mechanical design
Ambient temperature
-10...+60 °C
Storing temperature
-25...+85 °C
Relative humidity
95 % non-condensing
Connection
Spring-loaded terminal connector,
detachable
Core cross-section
1 mm² (grid 2.54)
2.5 mm
2
(grid 7.62)
Protection DIN EN 60529
IP 65 (face)
Operation / keypad
3 softkeys below bezel
Housing type
Built-in housing
Dimensions W x H x L
48 x 24 x 106 mm
Mounting
Front panel installation by clip frame
Material
Housing: Polycarbonate, UL 94V-0
Weight approx.
50 g