4.1 Input configuration

Selecting the input signal
Voltag input 10...600 VAC
Magnetic sensor
Namur
PNP
NPN
TTL
Contact input (20 Hz max.)

Sensor supply (*)
12 V for encoder and proximity switch
8 V for Namur Sensor
5 V TTL

(*) This programming line is not available at input signal selection

-1-, -2-, -7- ; In this case sensor supply is predefined to be 5 V.

4.2 Display configuration

Selection: Display / mode of measuring principle
Frequency display (4.2.1)
Tachometer (4.2.2)
Display scaling (4.2.3)

Depending on the selection, subsequent programming lines will

only provide the related chapter. Example: Selection FrEC will only

provide chapter 4.2.1 and no longer 4.2.2 and 4.2.3

4.2.1 Displaying frequency
Input frequency is in Hz.
Decimal point
No decimal point
0.1 Decimal point at first digit
0.01 Decimal point at second digit.

4.2.2 Tachometer
Indication of rpm or speed per minute.
Pulse evaluation
Required input of pulse number per displayed unit (e.g. pulses/meter

or pulses/revolution….)

Permitted range: 1 to 9999.

Example: To indicate speed as rpm with 500 ppr, enter pulse evaluati-

on factor 500.