3) GeoGauge will display, in sequence:

• Signal to Noise ratio (SNR) in dB [The stiffer the material, the

closer this value will be to 10, indicating that more than usual

attention should be paid to seating.]

• The standard deviation (5d) of all 25 frequency dependent

stiffness measurements relative to the displayed (average)

value of stiffness [This number will be small for soft materials

( ~ 1 MN/m) and larger for hard materials (~ 5 MN/m). A large

change in this number between test locations for a given

material may indicate improper seating (e.g., from 1.5 to

3 MN/m). A measurement should be repeated at such a

location to assure proper seating. If the measurement does not

change, then it is a true representation of the material.]

• Stiffness or Young’s modulus or fraction of stiffness Target

• Ready for next measurement (last measurement value

still displayed)

• Remove The GeoGauge From The Test Location

1) Examine the spot and ensure good foot contact

(see GeoGauge Seating).

2) Clean any soil off of the foot that may have been caked on in the

course of testing.

• Store Data (press “SAVE” button)

The measurement ID will be assigned to the stored data. The

GeoGauge will store data for 500 measurements as displayed

(Operational Mode). Only the first 20 measurements stored will also

include the complex, frequency dependent components of

displayed data (Research Mode).

• Turn The GeoGauge Off (press “OFF” button)

When done for the day, turn off to save battery power.

• Transfer Data (via optional Infrared interface)

Download data to a PC per GeoGauge Data Download Guide

(see Appendix 5).