56- Electric Latch Retraction Exit Devices
Installation and Wiring Instructions
With Optional 53- Latchbolt; 55- Request to Exit;
and TL- (SARGuide) Connection Instructions
FOR INSTALLATION ASSISTANCE CONTACT SARGENT • 1-800-810-WIRE (9473) • www.sargentlock.com
6. POWER MODE Troubleshooting
Prior to electrical troubleshooting, confirm that the mechanical system properly functions; i.e., that the push bar fully retracts
all latches and the door opens freely. Refer to applicable Sargent 80 Series Exit Device product instruction sheet to correct
mechanical installation issues.
IMPORTANT: *ALWAYS disconnect power before making any mechanical adjustments to the system.
The push rail does not move when 24V input is applied:
o Check inputs to confirm proper voltage and wiring orientation (Fig. 6 ElectroLynx
POWER MODE
Installation
).
o Remove end cap from rail and confirm that LED is blinking steadily when power is applied. If not, refer to LED signaling.
Note: When configured in POWER MODE, power is released to lock the device (LED will not blink when power is released).
o Confirm DIP switch position 3 is set to ON.
The push rail does not fully retract or push rail retracts completely and holds but does not open door
o *Verify mechanical installation and correct as necessary:
- Is excessive force required to depress the push bar?
- Are latches fully clearing the strikes when mechanically cycled?
The push rail retracts and unlocks electrically but does not relock:
o Physically disconnect power from rail and confirm that input is off.
o *Check for mechanical interference (e.g., warped door, lack of shims, misalignment of rail, etc.).
o *Was a motor kit (M56) installed? Verify the rail assembly.
Rail behaves abnormally (multiple cycles, clicking, delayed retraction, etc.):
o Remove end cap from rail and confirm that LED is blinking steadily when power is applied. If not, refer to LED signaling.
Note: When configured in POWER MODE, power is released to lock the device (LED will not blink when power is released).
For applications using automatic operator(s): Door(s) fail to unlock before doors begin to open:
o Adjust timing of operator to allow 750ms for the rail to fully retract.
53- switch wiring: The design requires normally open functionality and the circuit is normally closed (or vice versa),
There is only a two-wire input for the 53- circuit. Normally open or normally closed configuration is set by toggling the DIP switches on the controller
bracket to the required position (refer to chart in section 4).
For additional installation assistance, please contact 1-800-810-WIRE (9473). When calling, please provide the following information to improve our
service (provide what you can):
o Your name and contact number.
o Sargent 80 Series Exit Device product type (e.g. 55- 56- 8810).
o Location and identification of the affected opening (e.g., site, building, and door number).
o Sargent order number (located on product box), if available.
o Power supply manufacturer and rated output (i.e., voltage and current).
o Method of operation (e.g.,
POWER MODE
).
o The number of devices connected to the power supply.
o Symptoms of problem (i.e., observed behavior).
SIgNaL
CauSE
TRoubLEShooTINg
Dark / Unlit
Controller microprocessor is not active
Confirm connections and incoming power
Steady Flashing
Normal operation
Check that POWER MODE switch is set
Solid Light
Input voltage is dropping out of operating range
Check wire run and power supply output
2 Flashes Followed by Pause
Retractor sensor problem
Call 800-810-WIRE for assistance
3 Flashes Followed by Pause
Motor mechanism problem
Call 800-810-WIRE for assistance
5. LED Signalling Chart