tekmar 664 Snow Detector & Melting Control Installation User Manual

Page 25

background image

25 of 36

©

2009 D

664

-

07/09

B1

ΔT Maximum The maximum ΔT for the snow
melting system.
PRIORITY ≠ NONE

10 to 70°F, OFF
(5 to 39°C, OFF)
Default = OFF

C1

Differential The differential for the snow
melting system.
Boil SENS = SUP

AUTO, 2 to 42°F
(AUTO, 1 to 23°C)
Default = AUTO

A

C1

Boiler Minimum The minimum temperature
allowed for the boiler target temperature.
Boil SENS ≠ NONE

OFF, 80 to 180°F
(OFF, 27 to 82°C)
Default = 140° (60°C)

C1

Fire Delay The time delay the control can expect
between the time the Boiler contact closes and
the boiler fi res.
Boil SENS = SUP

0:00 to 3:00 minutes
Default = 0:10 min

C1

Boiler Mass The thermal mass characteristics of
the boiler(s) that is being used.
Boil SENS = SUP

LITE, MED, HEVY
Default = MED

C1

Stage 1 Selects stage 1 as operational or not.
Boil SENS = SUP

AUTO, OFF
Default = AUTO

C1

Stage 2 Selects Stage 2 as operational or not.
Boil SENS = SUP

AUTO, OFF
Default = OFF

C1

Rotate Sets the rotation time for the stages.
This item is used by the Equal Run Time
Rotation function.
Boil SENS = SUP

10 to 72 hours,
OFF
Default = 48 hr

A

Exercise The frequency with which the control
exercises the pumps and valves that are operated
by the control.

30 to 240 hours,
(in 10 hour steps)
Default = 70 hr

Item Field

Access
Level

Description

Range

Actual

Setting

Section

LT

D

USER

INS

T

AD

V

664 Adjust Menu (3 of 3)