tekmar 557 Thermostat Installation User Manual
Page 12

© 2014
557_D - 09/14
12 of 52
A Watts Water Technologies Company
Setting
Display
WARM WEATHER SHUT DOWN
Set the outdoor air temperature at which heating is
suspended during the event.
Access Level: Installer
Range: CTRL (control), 40 to
100°F (4.5 to 38.0°C), OFF
Conditions: An outdoor sensor must be available
and Schedules are in use or Scenes is set to All or
Guest.
Default: CTRL
SET COOL ROOM
Set the room cooling temperature for the event.
Access Level: Installer, User
Range: 50 to 100°F (10.0 to
38.0°C)
Conditions: Always
Default: 78°F (25.5°C)
SET COOL ROOM
Set the room cooling temperature for the event.
Access Level: Installer, User
Range: 50 to 100°F (10.0 to
38.0°C)
Conditions: Requires that Schedules are in use or
Scenes is set to All or Guest.
Default: 85°F (29.5°C)
SET COOL ROOM AWAY
Set the room cooling temperature during the Away
scene.
Access Level: Installer
Range: 50 to 100°F (10.0 to
38.0°C)
Conditions: Scenes is set to Away, All or Guest.
Default: 85°F (29.5°C)
COOL MINIMUM ROOM LIMIT
Set the minimum room cooling limit while in the
event.
Access Level: Installer
Range: 50 to 100°F (10.0 to
38.0°C)
Conditions: Always available.
Default: 50°F (10.0°C)
COOL MINIMUM ROOM LIMIT
Set the minimum room cooling limit while in the
event.
Access Level: Installer
Range: 50 to 100°F (10.0 to
38.0°C)
Conditions: Always available.
Default: 50°F (10.0°C)
Set Temp Menu (2 of 4)