Setting

Display

SET HEAT FLOOR

Set the floor heating temperature while in the
event.

Floor

Access Level: Installer, User

Range: 40 to 122°F (4.5 to 50.0°C)

Conditions: Room Sensor set to OFF and Sensor
1 or Sensor 2 set to Floor, and Schedules are in
use or Scenes are set to All or Guest.

Default: 65°F (18.5°C)

WARM WEATHER SHUT DOWN

Set the outdoor air temperature at which heating is
suspended during the event.

Access Level: Installer

Range: CTRL (control), 40 to
100°F (4.5 to 38.0°C), OFF

Conditions: Always available

Default: CTRL

WARM WEATHER SHUT DOWN

Set the outdoor air temperature at which heating is
suspended during the event.

Access Level: Installer

Range: CTRL (control), 40 to
100°F (4.5 to 38.0°C), OFF

Conditions: Requires that Schedules are in use or
Scenes is set to All or Guest.

Default: CTRL

FLOOR MINIMUM

Set the floor heating temperature while in the
event.

Access Level: Installer, User

Range: OFF, 40 to 122°F (4.5 to
50.0°C)

Conditions: Sensor 1 or Sensor 2 set to Floor, and
either Room Sensor set to ON, or Room Sensor
set to OFF while Sensor 1 or 2 is set to Room.

Default: 72°F (22.0°C)

FLOOR MINIMUM

Set the floor heating temperature while in the
event.

Access Level: Installer, User

Range: OFF, 40 to 122°F (4.5 to
50.0°C)

Conditions: Sensor 1 or Sensor 2 set to Floor, and
either Room Sensor set to ON, or Room Sensor
set to OFF while Sensor 1 or 2 is set to Room,
Schedules are in use or Scenes are set to All or
Guest.

Default: OFF

Set Temp Menu (2 of 3)