Setting
Display
SET HEAT FLOOR
Set the floor heating temperature while in the
event.
Floor
Access Level: Installer, User
Range: 40 to 122°F (4.5 to 50.0°C)
Conditions: Room Sensor set to OFF and Sensor
1 or Sensor 2 set to Floor, and Schedules are in
use or Scenes are set to All or Guest.
Default: 65°F (18.5°C)
WARM WEATHER SHUT DOWN
Set the outdoor air temperature at which heating is
suspended during the event.
Access Level: Installer
Range: CTRL (control), 40 to
100°F (4.5 to 38.0°C), OFF
Conditions: Always available
Default: CTRL
WARM WEATHER SHUT DOWN
Set the outdoor air temperature at which heating is
suspended during the event.
Access Level: Installer
Range: CTRL (control), 40 to
100°F (4.5 to 38.0°C), OFF
Conditions: Requires that Schedules are in use or
Scenes is set to All or Guest.
Default: CTRL
FLOOR MINIMUM
Set the floor heating temperature while in the
event.
Access Level: Installer, User
Range: OFF, 40 to 122°F (4.5 to
50.0°C)
Conditions: Sensor 1 or Sensor 2 set to Floor, and
either Room Sensor set to ON, or Room Sensor
set to OFF while Sensor 1 or 2 is set to Room.
Default: 72°F (22.0°C)
FLOOR MINIMUM
Set the floor heating temperature while in the
event.
Access Level: Installer, User
Range: OFF, 40 to 122°F (4.5 to
50.0°C)
Conditions: Sensor 1 or Sensor 2 set to Floor, and
either Room Sensor set to ON, or Room Sensor
set to OFF while Sensor 1 or 2 is set to Room,
Schedules are in use or Scenes are set to All or
Guest.
Default: OFF
Set Temp Menu (2 of 3)