tekmar 552 Thermostat Installation User Manual

Page 14

background image

© 2014

552_D - 09/14

14 of 44

A Watts Water Technologies Company

Set Temp Menu (1 of 3)

Setting

Display

SET HEAT ROOM

Set the room heating temperature during the
event.

Room

Access Level: Installer, User

Range: 40 to 95°F (4.5 to 35.0°C)

Conditions: Room Sensor set to ON or Sensor 1 or
Sensor 2 set to Room.

Default: 70°F (21.0°C)

SET HEAT ROOM

Set the room heating temperature during the
event.

Room

Access Level: Installer, User

Range: 40 to 95°F (4.5 to 35.0°C)

Conditions: Room Sensor set to ON or Sensor 1 or
Sensor 2 set to Room, and Schedules are in use
or Scenes are set to All or Guest.

Default: 65°F (18.5°C)

SET HEAT ROOM AWAY

Set the room heating temperature during the Away
scene.

Room

Access Level: Installer, User

Range: 40 to 95°F (4.5 to 35.0°C)

Conditions: Room Sensor set to ON or Sensor 1 or
Sensor 2 set to Room, and Scenes is set to Away,
All or Guest.

Default: 62°F (16.5°C)

ROOM MAX

Set the maximum room heating limit while in the

event.

Access Level: Installer

Range: 40 to 95°F (4.5 to 35.0°C)

Conditions: Room Sensor set to ON or Sensor 1 or
Sensor 2 set to Room.

Default: 85°F (29.5°C)

ROOM MAX

Set the maximum room heating limit while in the
event.

Access Level: Installer

Range: 40 to 95°F (4.5 to 35.0°C)

Conditions: Room Sensor set to ON or Sensor 1 or
Sensor 2 set to Room, and Schedules are in use
or Scenes are set to All or Guest.

Default: 85°F (29.5°C)

SET HEAT FLOOR

Set the floor heating temperature while in the
event.

Floor

Access Level: Installer, User

Range: 40 to 122°F (4.5 to 50.0°C)

Conditions: Room Sensor set to OFF and Sensor
1 or Sensor 2 set to Floor.

Default: 72°F (22.0°C)