beautypg.com

Testing the sensor wiring, Testing the control wiring – tekmar 400 House Control Installation User Manual

Page 9

background image

© 2013

400_D - 09/13

9 of 32

A good quality test meter capable of measuring up to 5,000
kΩ (1 kΩ = 1000 Ω) is required to measure the sensor
resistance. In addition to this, the actual temperature must
be measured with either a good quality digital thermometer,
or if a thermometer is not available, a second sensor can
be placed alongside the one to be tested and the readings
compared.
First measure the temperature using the thermometer and
then measure the resistance of the sensor at the control.
The wires from the sensor must not be connected to the
control while the test is performed. Using the chart below,

estimate the temperature measured by the sensor. The
sensor and thermometer readings should be close. If the
test meter reads a very high resistance, there may be a
broken wire, a poor wiring connection or a defective sensor.
If the resistance is very low, the wiring may be shorted,
there may be moisture in the sensor or the sensor may
be defective. To test for a defective sensor, measure the
resistance directly at the sensor location.
Do not apply voltage to a sensor at any time as damage
to the sensor may result.

Testing the Sensor Wiring

Temperature

Resistance

Temperature

Resistance

Temperature

Resistance

Temperature

Resistance

°F

°C

°F

°C

°F

°C

°F

°C

-50

-46

490,813

20

-7

46,218

90

32

7,334

160

71

1,689

-45

-43

405,710

25

-4

39,913

95

35

6,532

165

74

1,538

-40

-40

336,606

30

-1

34,558

100

38

5,828

170

77

1,403

-35

-37

280,279

35

2

29,996

105

41

5,210

175

79

1,281

-30

-34

234,196

40

4

26,099

110

43

4,665

180

82

1,172

-25

-32

196,358

45

7

22,763

115

46

4,184

185

85

1,073

-20

-29

165,180

50

10

19,900

120

49

3,760

190

88

983

-15

-26

139,400

55

13

17,436

125

52

3,383

195

91

903

-10

-23

118,018

60

16

15,311

130

54

3,050

200

93

829

-5

-21

100,221

65

18

13,474

135

57

2,754

205

96

763

0

-18

85,362

70

21

11,883

140

60

2,490

210

99

703

5

-15

72,918

75

24

10,501

145

63

2,255

215

102

648

10

-12

62,465

80

27

9,299

150

66

2,045

220

104

598

15

-9

53,658

85

29

8,250

155

68

1,857

225

107

553

Testing the Control Wiring

Testing the Power

-----------------------------

-----------------------------

If the control display does not turn on, check the Input
Power wiring terminals using an electrical multimeter. The
voltage should measure between 21.6 to 26.4 V (ac). If the
voltage is below this range, measure the line voltage side
of the transformer. The voltage should measure between
103.5 to 126.5 V (ac).

Testing the Thermostats ----------------------

----------------------

If the thermostat display turns on, this indicates that the
thermostat is operating correctly and there are no electrical
issues. In the event that the display is off, or the display is
cycling on and off, follow this procedure.

1. Remove the tN2 wires from the thermostat.
2. Use an electrical meter to measure DC voltage between

the tN2 terminals.

If the DC voltage is 0 V (dc) for 20 seconds, then there is
an open or short circuit in the tN2 wires. If the DC voltage
is 0 V (dc) for 10 seconds and then is 23 to 24 V (dc) for 5
seconds, this indicates the wiring is correct.
3. Connect the thermostat to the tN2 wires from a zone

on a House Control, Wiring Center, or Zone Manager.

4. If the thermostat display is off, or is cycling on and off,

move the thermostat to the next available zone on the
House Control, Wiring Center, or Zone Manager.

If the thermostat display remains permanently on, there
may be a fault with the previously tried zone on the House
Control, Wiring Center, or Zone Manager.

If the thermostat display continues to be off, or is cycling
on and off, there may be a fault on the thermostat.
If a fault is suspected, contact your tekmar sales
representative for assistance.

User Test --------------------------------------

--------------------------------------

The User Test is found in the Toolbox menu of the control.
Press the Menu button to access the Toolbox Menu. Press
the Item button to locate the User Test.
Start the test sequence by going to the User Test item and
pressing the ‘Up’ arrow button.
Pause the test sequence by pressing the Item button. To
advance to the next step, press the Item button again.
If the test sequence is paused for more than five minutes,
the control exits the entire test routine and returns to normal
operation.
To advance to a particular step, repeatedly press and
release the Item button to display the appropriate device.
User Test Sequence
Step 1 Zone 1 turns on for 10 seconds.
Step 2 Zone 2 turns on for 10 seconds.
Step 3 Zone 3 turns on for 10 seconds.
Step 4 Zone 4 turns on for 10 seconds.
Step 5 The DHW pump turns on for 10 seconds.
Step 6 The boiler system pump turns on for 10

seconds.

Step 7 During the boiler test step, zone relays 1 through

4 turn on, and the boil system pump turns on.