Quick Setup

The quick setup can be used for both outdoor reset and setpoint operation. To enter the installer programming mode, set the

Advanced /

Installer DIP switch to Installer.

OUTDOOR RESET

Access the ADJUST menu by pressing and holding simultaneously for 1 second, the

Item, and buttons (all three buttons).

The display will now show the word ADJUST in the top right corner.

The ROOM adjustment is the first item displayed. Use the or button to set the ROOM temperature. The
ROOM setting is set to the desired room air temperature.

Note: To increase or decrease space temperature, only adjust the ROOM setting.

Press and release the

Item button to advance to the OUTDR DSGN adjustment. Use the or button to

set the outdoor design temperature. The OUTDR DSGN setting is set to the typical coldest temperature of
the year.

Press and release the

Item button to advance to the Terminal Unit adjustment. Use the or button to select

the desired terminal unit. The terminal unit number corresponds to the type of terminal that is being used.
The table below lists the terminal units and their default values.

Press and release the

Item button to advance to the units adjustment. Use the or button to set the scale

to

°F or °C.

To exit the ADJUST menu, press and release the

Item button to advance to the ESC item. Then either press

the or button, or leave the buttons alone for 20 seconds.

SETPOINT CONTROL

Access the ADJUST menu by pressing and holding simultaneously for 1 second, the

Item, and buttons (all three buttons).

The display will now show the word ADJUST in the top right corner.

Press and release the

Item button to advance to the OUTDR DSGN adjustment. Press and hold the button

until OFF is displayed.

Press and release the

Item button to advance to the MIX TARGET adjustment. Use the or button to select

the desired temperature. The MIX TARGET setting is set to the desired setpoint supply temperature.

Press and release the

Item button to advance to the units adjustment. Use the or button to set the scale

to

°F or °C.

To exit the ADJUST menu, press and release the

Item button to advance to the ESC item. Then either press

the or button, or leave the buttons alone for 20 seconds..

150

°F (66°C)

170

°F (77°C)

MIX DSGN
MIX MAX

Terminal Unit

190

°F (88°C)

210

°F (99°C)

High Mass Radiant

(1)

120

°F (49°C)

140

°F (60°C)

Low Mass Radiant

(2)

Fancoil

(3)

140

°F (60°C)

160

°F (71°C)

Fin-tube Convector

(4)

180

°F (82°C)

200

°F (93°C)

Radiator

(5)

160

°F (71°C)

180

°F (82°C)

Baseboard

(6)

ADJUST

ROOM

°

F

ADJUST

DSGN

OUTDR

°

F

ADJUST

°

F

ADJUST

ADJUST

DSGN

OUTDR

ADJUST

TARGET

MIX

°

F

ADJUST

°

F

ADJUST

Terminal Unit

ADJUST