© 2010 D 270 - 08/10

20 of 24

Adjust Menu (2 of 2)

Display

Description

Range

Section

Installer

Ad

vanced

Actual

Setting

B3

Boiler Modulation Selects either a 2 to 10 V (dc) or a
0 to 10 V (dc) output signal.

2:10, 0:10
Default = 0:10

B3

Minimum Modulation The minimum percent modulation
of the burner.

0 to 50%
Default = 0%

B3

Maximum Modulation The maximum percent modulation
of the burner.

50 to 100%
Default = 100%

E1
E2

DHW Mode Selects the DHW mode of operation.

1 (parallel, no priority),

2 (parallel, priority),

3 (pri-sec, no priority),
4 (pri-sec, priority)
Default = 1

DHW Exchange Occupied The minimum boiler supply
temperature to the DHW heat exchanger during the
Occupied period.

OFF, 100 to 220°F
(OFF, 38 to 104°C)
Default = 180°F (82°C)

DHW Exchange Unoccupied Selects whether or not a
DHW demand will be responded to during the UnOccupied
period.

OFF, On
Default = OFF

WWSD Occupied The system’s warm weather shut down
temperature during the Occupied period.

35 to 100°F, OFF
(2 to 38°C, OFF)
Default = 70°F (21°C)

WWSD Unoccupied The system’s warm weather shut
down temperature during the Unoccupied period.

35 to 100°F, OFF
(2 to 38°C, OFF)
Default = 60°F (16°C)

C1

Primary Pump Purge The maximum length of time that
the primary pump will continue to operate after the boiler
demand has been removed.

OFF, 0:10 to 19:55 min.
(5 second increments)

Default = 0:20 min

C1

Boiler Pump Purge The length of time that the boiler
pump will continue to run after the boiler demand is
removed.

OFF, 0:10 to 19:55 min.
(5 second increments)

Default = 0:20 min

The units of measure that all of the temperatures are to be
displayed in by the control.

°F,°C
Default = °F