Terminal Blocks

IP67 Housing

IP20 Housing

PWR

GND
DO6

DO5
DO4

DO3
DO2

DO1

PWR

GND
DI6

DI5
DI4

DI3
DI2

DI1

DI1
DI2
DI3
DI4
DI5
DI6

V-
V-

V+

V+

DO6

DO5

DO1
DO2
DO3
DO4

Tx/+
Rx/-

DIx. Discrete IN x.
DOx. Discrete OUT x.
GND. Ground/dc common connection.
PWR. Power, 10 to 30V dc power connection.
RX/-. Serial comms line
TX/+. Serial comms line
V+. Power, 10 to 30V dc power connection.
V-. Ground/dc common connection.

Wiring Diagrams for Discrete Inputs

Connecting dc power to the communication pins will cause permanent damage. For the DX8x...C models, PWR in the wiring diagram
refers to V+ on the wiring board and GND in the wiring diagram refers to V- on the wiring board.

Discrete Input Wiring for PNP Sensors

Discrete Input Wiring for NPN Sensors

DIx

PWR

10-30V dc

DIx

GND

dc common

Wiring Diagrams for Discrete Outputs

Connecting dc power to the communication pins will cause permanent damage. For the DX8x...C models, PWR in the wiring diagram
refers to V+ on the wiring board and GND in the wiring diagram refers to V- on the wiring board.

Discrete Output Wiring (PNP)

DOx

GND

PWR

10-30V dc

Load

dc common

LED Behavior for the Gateways

After powering up and binding the Gateway and its Nodes, verify all devices are communicating properly. When testing communication
between the Gateway and Node, all radios and antennas should be at least two meters apart or the communications may fail.

LED 1

LED 2

Gateway Status

(solid green)

Power ON

(flashing red)

(flashing red)

Device Error

(flashing yellow)

Modbus Communication Active

(flashing red)

Modbus Communication Error

For Gateway and Ethernet Bridge systems, active Modbus communication refers to the communication between the Gateway and the
Ethernet Bridge. For GatewayPro systems, the Modbus communication LEDs refer to the communication internal to the GatewayPro. For

SureCross DX80 Gateway for M-GAGEs

P/N 134303 Rev. H