1. Unscrew the four screws that mount the cover to the bottom housing.
2. Remove the cover from the housing without damaging the ribbon cable or the pins the cable plugs into.
3. Gently unplug the ribbon cable from the board mounted into the bottom housing.
4. Remove the black cover plate from the bottom of the device's cover.

The DIP switches are located behind the rotary dials.

After making the necessary changes to the DIP switches, place the black cover plate back into position and
gently push into place. Plug the ribbon cable in after verifying that the blocked hole lines up with the missing
pin. Mount the cover back onto the housing.

DIP Switch Settings

Switches

Device Settings

1

2

3

4

5

6

7

8

Rotary dial address mode

OFF*

Extended address mode

ON

Inputs sourcing (PNP)

OFF*

Inputs sinking (NPN)

ON

Node 1 baseline filter OFF

OFF*

Node 1 baseline filter ON

ON

Node 1: threshold = 100, hysteresis = 30

OFF*

OFF*

Node 1: threshold = 150, hysteresis = 30

OFF

ON

Node 1: threshold = 200, hysteresis = 30

ON

OFF

Node 1: threshold = 50, hysteresis = 15

ON

ON

Node 2 baseline filter OFF

OFF*

Node 2 baseline filter ON

ON

Node 2: threshold = 100, hysteresis = 30

OFF*

OFF*

Node 2: threshold = 150, hysteresis = 30

OFF

ON

Node 2: threshold = 200, hysteresis = 30

ON

OFF

Node 2: threshold = 50, hysteresis = 15

ON

ON

* Default configuration
Address Mode
The SureCross wireless devices may use one of two types of addressing modes: rotary dial addressing or extended addressing. In
rotary dial address mode, the left rotary dial establishes the network ID and the right rotary dial sets the device ID. The wireless network
is restricted to a maximum of 16 devices.
Extended address mode uses a security code to "bind" Nodes to a specific Gateway. Bound Nodes can only send and receive informa-
tion from the Gateway to which they are bound. In extended address mode, wireless networks may contain up to 48 radio devices. For
more information on extended address mode, refer to the SureCross™ Wireless I/O Network product manual.
The device ships in rotary dial address mode by default, with the DIP switch in the OFF position. To use extended address mode, change
the DIP switch to the ON position.
Baseline Threshold/Filter (M-GAGE)
Under normal conditions, the ambient magnetic field fluctuates. When the magnetic field readings drift below a threshold setting, the
baseline or drift filter uses an algorithm to slowly match the radio device’s baseline to the ambient magnetic field.
Discrete Input Type
Select the type of discrete input sensors to use with this device: sourcing (PNP) sensors or sinking (NPN) sensors.