Banner SureCross DX80 Wireless Networks User Manual
Page 3
Switches
Device Settings
1
2
3
4
5
6
7
8
Sensor 1: 6 inputs, 6 outputs (Primary and secondary
I/O 1-3)
OFF
ON
ON
Sensor 1 & 2: 3 inputs, 0 outputs (Primary inputs 1-3)
ON
OFF
OFF
Sensors 1 & 2: 1 input, 0 outputs (Primary input 1), and
Discrete IN 1 through 4**
ON
OFF
ON
Sensors 1 & 2: 2 inputs, 0 outputs (Primary inputs 1-2),
Discrete IN 1, and Discrete IN 2**
ON
ON
OFF
Sensors 1 & 2: 3 inputs, 3 outputs (Primary I/O 1-3)
ON
ON
ON
Sample/Report Rates: 16 seconds
OFF*
OFF*
OFF*
Sample/Report Rates: 64 seconds
OFF
OFF
ON
Sample/Report Rates: Sample on Demand
OFF
ON
OFF
Sample/Report Rates: 125 milliseconds
OFF
ON
ON
Sample/Report Rates: 500 milliseconds
ON
OFF
OFF
Sample/Report Rates: 1 seconds
ON
OFF
ON
Sample/Report Rates: 4 seconds
ON
ON
OFF
Sample/Report Rates: 8 seconds
ON
ON
ON
* Default configuration
** All discrete inputs are sinking inputs with sample rates of 62.5 milliseconds and change of state reporting.
Address Mode
The SureCross wireless devices may use one of two types of addressing modes: rotary dial addressing or extended addressing. In
rotary dial address mode, the left rotary dial establishes the network ID and the right rotary dial sets the device ID. The wireless network
is restricted to a maximum of 16 devices.
Extended address mode uses a security code to "bind" Nodes to a specific Gateway. Bound Nodes can only send and receive informa-
tion from the Gateway to which they are bound. In extended address mode, wireless networks may contain up to 48 radio devices. For
more information on extended address mode, refer to the SureCross™ Wireless I/O Network product manual.
The device ships in rotary dial address mode by default, with the DIP switch in the OFF position. To use extended address mode, change
the DIP switch to the ON position.
Modbus/User Configuration Tool (UCT) or DIP Switch Configured
In Modbus/UCT Configured mode, the device parameters are changed using the User Configuration Tool (UCT) or a Modbus command.
All DIP switch positions are ignored. In DIP Switch Configured mode, use the DIP switches to configure the parameters listed in the table.
Register Configuration
The Node’s Modbus registers can be configured using DIP switches 3 through 5, allowing for some custom configurations. Each
FlexPower Serial Sensor has a defined set of template registers listed in the device’s data sheet. For example, the FlexPower Tempera-
ture/Humidity sensor has three defined primary registers a user can access: register 1 for relative humidity, register 2 for the temperature
in degrees C, and register 3 for the temperature in degrees F.
When using the default switch settings (OFF, OFF, OFF), the Node reads all three registers and places the contents in the first three
Modbus registers associated with the Node. With the switch settings set to “001” (OFF, OFF, ON), only the relative humidity information
is read and placed into Modbus register 1.
Integrated battery devices support only one serial sensor device per Node. FlexPower Serial Nodes with internal wiring terminals support
up to two serial sensor devices per Node. Use the DIP switches to define the Modbus register use for both serial sensor devices.
Some FlexPower Serial Sensor devices have more than three primary inputs; these inputs are referred to as secondary inputs or outputs.
The DIP switch configurations allow for up to six inputs and six outputs for a single device.
SureCross DX80 Serial Node with Integrated Battery
P/N 137322 Rev. F
www.bannerengineering.com - tel: 763-544-3164
3