beautypg.com

Dimensions, Hookups, Accessories – Banner U-GAGE T30U—Level Control User Manual

Page 7: Cordsets

background image

Dimensions

M30 x 1.5

Thread

ø 40.0 mm

(1.57")

Cabled Models

Quick-Disconnect Models

Jam Nut

(Supplied)

45.0 mm

(1.77")

ø 15 mm

(0.59")

11.5 mm

(0.45")

51.5 mm

(2.03")

66.5 mm

(2.62")

Hookups

Shield*

12-24V dc

+

1

3

2

4

5

Remote
Teach

Output 1

Output 2

Figure 9. Cabled NPN

Shield*

12-24V dc

+

1

3

2

4

5

Remote
Teach

Output 1

Output 2

Figure 10. Cabled PNP

1 = Brown
2 = White
3 = Blue
4 = Black
5 = Gray

Cable and QD hookups are functionally identical.
It is recommended that the shield wire is connected to earth ground or dc common.

Accessories

Cordsets

5-Pin Threaded M12/Euro-Style Cordsets with Shield

Model

Length

Style

Dimensions

Pinout

MQDEC2-506

1.83 m (6 ft)

Straight

44 Typ.

ø 14.5

M12 x 1

2

3

4

1

5

1 = Brown
2 = White
3 = Blue
4 = Black
5 = Gray

MQDEC2-515

4.57 m (15 ft)

MQDEC2-530

9.14 m (30 ft)

MQDEC2-550

15.2 m (50 ft)

MQDEC2-506RA

1.83 m (6 ft)

Right-Angle

32 Typ.

[1.26"]

30 Typ.

[1.18"]

ø 14.5 [0.57"]

M12 x 1

MQDEC2-515RA

4.57 m (15 ft)

MQDEC2-530RA

9.14 m (30 ft)

MQDEC2-550RA

15.2 m (50 ft)

U-GAGE® T30U Series Sensors - Pump-In/Pump-Out

P/N 063974 Rev. C

www.bannerengineering.com - tel: 763-544-3164

7