Banner U-GAGE T30U—Level Control User Manual
Page 4
![background image](/manuals/587243/4/background.png)
Program Second Output
Repeat as needed for other output.
Teaching Identical (Complementary) Window Limits for Both Outputs
A Single Pair of Sensing Window Limits
is taught; only one output is on at any time
Dead Zone
Sensing
Range
Limits for
Both Outputs
1 and 2
Liquid levels here energize Output 2
Liquid levels here
energize Output 1
Figure 4. Programming one pair of sensing window limits, com-
plementary outputs
Only one output conducts at any time in response to the target distance. Under no conditions will
both outputs conduct at the same time; see
on page 1 and the figure on the left.
The distance between the taught near and far limits must be at least 10 mm in this complementa-
ry mode for proper sensor operation.
Push Button
Remote Wire
0.04 sec. < T < 0.8 sec.
Procedure
Result
Procedure
Result
Programming Mode
• Press and hold both push but-
tons (or press and hold one and
then the other)
3
>2 sec.
• Green Power LED turns OFF
• Both Output LEDs turn ON Yellow
• Sensor waits for first limit
• No action required
Teach First Limit
• Position the target for the first
limit
• “Click” either push button
• After a short delay, the Yellow
LEDs flashes
• Sensor learns first limit and waits
for second limit
• Position the target for the first limit
• Triple-pulse the remote line
T
T
T
T
T
• Green Power LED turns OFF
• Both Output LEDs turn ON Yellow
• After a short delay, the Yellow LEDs
flash
Teach Second Limit
• Position the target for the sec-
ond limit
• “Click” either push button
• After a short delay, the Green
Power LED goes ON
• Sensor learns second limit and re-
turns automatically to Run mode
• Position the target for the second limit
• Single-pulse the remote line
T
• After a short delay, the Green Power
LED turns ON
• Sensor learns second limit and re-
turns automatically to Run mode
3
Sensor will return to RUN mode if first TEACH condition is not registered within 120 seconds.
U-GAGE® T30U Series Sensors - Pump-In/Pump-Out
4
www.bannerengineering.com - tel: 763-544-3164
P/N 063974 Rev. C