Teaching Separate Window Limits for Each Output

Each output conducts in its respective manner (either pump-in or pump-out) independently, in re-
sponse to the target distance. The two outputs may overlap or may be completely independent. For
fill-level applications, set the window limits for Output 2 (pump-in) farther from the sensor than for
Output 1 (pump-out); see figure on the right.
The distance between the taught near and far limits for each output must be at least 10 mm.
To readjust window limits for either output, follow the teach procedure for that output only.

Pump-In limits Farther
than Pump-Out Limits

Dead Zone

Sensing

Range

Pump-Out

Output 1

Limits

Pump-Out

Output 1

Limits

Pump-In

Output 2

Limits

Pump-In

Output 2

Limits

Liquid levels here energize Output 2

Liquid levels here energize Output 2

Liquid levels here

energize Output 1

Liquid levels here

energize Output 1

Sensing

Range

Dead Zone

Pump-In limits Nearer
than Pump-Out Limits

Figure 3. Programming separate sensing window limits for

each output

Push Button

Remote Wire

0.04 sec. < T < 0.8 sec.

Procedure

Result

Procedure

Result

Programming Mode

• Push and hold push but-

ton for selected output

2

>2 sec.

• Green Power LED turns OFF
• Corresponding Output LED

turns ON Yellow

• Sensor waits for first limit

• No action required

Teach First Limit

• Position the target for

the first limit

• “Click” the same push

button

• After a short delay, the Yel-

low LED flashes

• Sensor learns first limit and

waits for second limit

• Position the target for the first limit

Output 1 (Pump-Out)

• Double-pulse the remote

line

T

T

T

Output 2 (Pump-In)

• Single-pulse the remote

line

T

• Green Power LED turns

OFF

• Corresponding Output LED

turns ON Yellow

• After a short delay, the Yel-

low LED flashes

Teach Second Limit

• Position the target for

the second limit

• “Click” the same push

button

• After a short delay, the

Green Power LED goes ON

• Sensor learns second limit

and returns automatically to
Run mode

• Position the target for the second limit
• Single-pulse the remote line

T

• After a short delay, the

Green Power LED turns ON

• Sensor learns second limit

and returns automatically to
Run mode

2

Sensor will return to RUN mode if first TEACH condition is not registered within 120 seconds.

U-GAGE® T30U Series Sensors - Pump-In/Pump-Out

P/N 063974 Rev. C

www.bannerengineering.com - tel: 763-544-3164

3