CommScope Redwood version 2.1 User Manual
Page 8
SSYSTEM INSTALLATION GUIDE
8
Redwood System Installation Guide v2.1
Redwood System Installation Guide
Note: Minimum branch circuit is required for a single engine, given the standard 80% de-rating.
Model Number
Operating Voltage
Current
Required
Minimum Branch
Circuit Required
Max Power
Consumption
RE64-2G-277 277
VAC,
50-60Hz
7A
10A
1580W
RE64-2G-120-250
120 VAC, 50-60Hz
16A
20A
1580W
200 – 250 VAC, 50-60Hz
10A
20A
1580W
The Engine also ships with power cords that are specific to geographic location and voltage. It is
important to specify country and voltage requirement when ordering.
IMPORTANT NOTES
•
The internal components are not field-serviceable.
• If any internal fuses require replacement, return the equipment to the manufacturer.
REDWOOD
UNIVERSAL ENGINE
RE64-2G-277
277V 15A
LOCKING NEMA
L7-15P
REDWOOD
UNIVERSAL ENGINE
RE64-2G-120-250
250V 20A
INLET
IEC 60320-C20