Variable speed motor drive: 6010 – Rockwell Automation 2LW3000 LonWorks Communication Option Module for VTAC 7 Drives User Manual
Page 54

7-2
LonWorks Module for VTAC 7 Drives
Figure 7.2 – Drive Object
Variable Speed Motor
Drive: 6010
M andatory
Network
Variables
Optional
Network
Variables
Manufacturer
Defined
Network
Variables
nv1
nviD rvSpee dStpt
S NV T_sw itch
nv2
nviD rvSpe edScale
SN VT_ lev_percent
nv6
nvoD rvCurnt
SN VT_am p
n v5
nvoD rvSpe ed
SN VT _lev_percent
nv11
nvoD rvStatus 2
SN VT_sta te
nv8
nvoDrvPw r
SN VT _pow er_kilo
nv9
nvoDrvRunHo urs
SN VT _tim e_hour
nv7
nvoDrvVolt
SN VT _volt
C onfigura tion P ro perties
nc1 7 - nciLocation (op tional)
nc50 - nciMa xSp eed (ma ndatory)
nc53 - nciMinSpeed (m anda tory)
nc48 - nciRcvHrtB t (optio nal)
nc49 - nciSnd HrtBt (m andatory)
nc52 - nciMinO utTm (optiona l)
nc158 - nciNm lSpe ed (m andatory)
nc159 - nciNm lFreq (m andatory)
nc160 - nciRam pUp Tm (m and ato ry )
nc161 nciRam pDow nTm (m andatory)
nc162 nciDrvSp eedScale (op tional)
M anu fa cturer defin ed Co nfig uration Pro perties
ncR A1 nciParR dAdr
ncR A2 nciParW riA dr
ncR A3 nciParW riD ata
ncR A4 nciJogR ef
ncR A5 nciCu rL im it
nv10
nvoD rvStatus 1
SN VT_sta te
nv12
nvoO CL _FB
SN VT_count
nv13
n voO CL_loo p_ou t
S NVT_lev_percent
nv14
nvoP aram
SN VT_count
nv4
nviO CL _enable
SNV T_sw itch
nv3
nviJogSel
SN VT_switch
nv15
nvoF ault1
SN VT_sta te
nv16
nvoF ault2
SN VT_sta te