2. System Requirements
The Valve Manager requires that certain aspects of the systems that it works with to be configured in a
consistent manner. In all such cases, the configuration is limited to the aspects that directly involve
valve testing.
2.1. Required Tags and Tag Naming Convention
In order to be able to automatically recognize and work with a valve, the Valve Manager requires that
certain variables associated with each valve follow a specified naming convention. The tags for such
variables consist of 2 parts: a valve identifier, followed by a suffix specific to the type of variable (i.e.
“valve01_VTS”, where “valve01” is the identifier and “_VTS” is the suffix). The valve identifier must be
the same for all tags related to a given valve. Additionally, certain tags require that a valid Modbus
address be defined.
The following table enumerates the required variables, their appropriate suffix, and the required
Modbus access.
Type
Attribute
Suffix
Modbus Access
Description
Boolean
Internal
_VTS
Read/Write
Valve Test Start
Integer
Internal
_ETM
Read/Write
End Time
Integer
Internal
_EST
Read/Write
End State
Integer
Internal
_VTM
Read Only
Valve Test Mode
Integer
Internal
_VT1
Read Only
Valve Test Transition Time 1
Integer
Internal
_VT2
Read Only
Valve Test Transition Time 2
Integer
Internal
_VT3
Read Only
Valve Test Transition Time 3
Integer
Internal
_VT4
Read Only
Valve Test Transition Time 4
Integer
Internal
_VT5
Read Only
Valve Test Transition Time 5
Boolean
Internal
_VTP
Not Required
Valve Test Permissive
Integer
Input
_MXI
Not Required
Selected Mux Channel
Integer
Input
_MXD
Not Required
Mux Channel Data
Integer
Output
_MXO
Not Required
Mux Channel Select
Boolean
Output
_VTO
Not Required
Valve Test Output
Integer
Output
_ETO
Not Required
End Time Output
Integer
Output
_ESO
Not Required
End State Output
Table 1 Tag Naming Convention