4.2. Module Status LEDs
There are six module status indicators on the module front panel: three Healthy, one Active, one
Standby, and one Educated. The Healthy indicators are controlled directly by each module slice. The
Active, Standby, and Educated indicators are controlled by the FPU. The FPU receives data from
each of the module slices. The FPU performs a 2-oo-3 vote on each data bit from the slices and sets
the indicators accordingly.
The module status indicator modes and their meanings are described as follows:
INDICATOR
STATE
DESCRIPTION
Healthy
Off
No power applied to the module.
Green
Slice is healthy.
Red – flashing
Fault present on the associated slice.
Red
Power applied to the associated slice.
Active
Off
Module is not in the Active state.
Green
Module is in the Active (or Maintain) state.
Red – flashing
Module is in the shutdown state.
Standby
Off
Module is not in the Standby state.
Green
Module is in the Standby state.
Red – flashing
Module is in the ‘passive’ shutdown state.
Educated
Off
Module is not educated.
Green
Module is educated.
Green – flashing
Education in progress.
Amber - Flashing
Active/standby changeover in progress
Table 22 Module Status LEDs