3. Application
3.1. Module Configuration
There is no configuration required to the physical output module. All configurable characteristics of the
module are performed using tools on the EWS and become part of the application or system.ini file
that is loaded into the TMR Processor. The TMR Processor automatically configures the output
module after applications are downloaded and during Active/Standby changeover.
The
IEC1131 TOOLSET
provides the main interface to configure the output module. Details of the
configuration tools and configuration sequence is provided in PD-8082B. There are three procedures
necessary to configure the output module. These are:
1. Define the necessary I/O variables for the field output data and module status data using the
Dictionary Editor of the
IEC1131 TOOLSET
.
2. Create an I/O module definition in the I/O Connection Editor for each I/O module. The I/O
module definition defines physical information, e.g. Chassis and Slot location, and allows
variables to be connected to the I/O channels of the module.
3. Using the Trusted
TM
System Configuration Manager, define custom LED indicator modes,
per-channel shutdown states, and other module settings.
3.2. T8449 Complex Equipment Definition
The T8449 I/O Complex Equipment Definition includes 8 I/O boards, referenced numerically by Rack
number:
Rack I/O Board
Description
Data
Type
Direction
No. of
Channels
OEM Parameters
-
-
-
1
DO_TEST
Output Command / Test Command
Boolean
Out
40
2
STATE
Field Output State
Integer
In
40
3
AI _MXIN
Output voltage / MUX data selection Integer
In
40
4
CI _MXDAT
Output current / MUX data
Integer
In
40
5
MXOUT
MUX data request
Integer
Out
20
6
ETM_EST
Max Test Time / Test End State
Integer
Out
40
7
LINEFLT
Line Fault Status
Boolean
In
40
8
DISCREP
Channel Discrepancy
Integer
In
3
9
HKEEPING
Housekeeping Registers
Integer
In
57
10
INFO
I/O Module Information
Integer
In
11
Table 3 Complex Equipment Definition