Table 19 rack 10: mux channels, Trusted, Module t8449 – Rockwell Automation T8449 Trusted TMR 24V dc Valve Monitor Module - 40 Channel User Manual
Page 33

Trusted
TM
Module T8449
Issue 13 Apr 10
PD-T8449
33
The following are valid index values for MXOUT. Indexes 10 to 15 are only available after a valve test
that either completes (reaches its goal state within the allotted time) or fails (dooes not reach the goal
state within the allotted time). After completion or end time, the timers will continue to run until the test
initiation command is removed. Later state transitions will be recorded up to 32.766 seconds.
MUX
Index
Description
0
Valve Test State
1
Time 1 (Test start or Command received to State 1)
2
Time 2 (Test start or Command received to State 2)
3
Time 3 (Test start or Command received to State 3)
4
Time 4 (Test start or Command received to State 4)
5
Time 5 (Test start or Command received to State 5)
6
Sampled ETIME
7
Sampled ESTATE
8
Feedback Input voltage
9
Raw feedback input voltage
10
Elapsed time since test start or command received
11
Time 1 (if state 1 was not reached by the end time)
12
Time 2 (if state 2 was not reached by the end time)
13
Time 3 (if state 3 was not reached by the end time)
14
Time 4 (if state 4 was not reached by the end time)
15
Time 5 (if state 5 was not reached by the end time)
Table 19 Rack 10: MUX Channels