Line monitoring and output states, Housekeeping, Fault detection/testing – Rockwell Automation T8449 Trusted TMR 24V dc Valve Monitor Module - 40 Channel User Manual
Page 11: Table 1 line monitoring fault status, Trusted, Module t8449

Trusted
TM
Module T8449
Issue 13 Apr 10
PD-T8449
11
1.5. Line monitoring and output states
The module automatically monitors the control output channel current and voltage to determine the
state of the output channel. The numerical output state and line fault status reported back to the
application is represented below.
Description
Numerical
Output State
Line Fault
Status
Field Fault
6
1
Field Short Circuit
5
1
Output Energised (On)
4
0
No Load, Field Open Circuit
3
1
Output De-energised (Off)
2
0
No Field Supply Voltage
1
1
Table 1 Line Monitoring Fault Status
The Field Fault condition is used to report cases where the output is commanded De-energized (Off),
but voltage is being supplied to the output circuit through some external source.
Default threshold values used for non line monitored inputs are as follows (in raw units)
Default = 1000, -1000, 3000, 3000, 5000, 5000, 7000, 7000
1.6. Housekeeping
The output module automatically performs local measurements of several on-board signals that can be
used for detailed troubleshooting and verification of module operating characteristics. Measurements
are made within each slice’s HIU and FIU.
1.7. Fault Detection/Testing
Extensive diagnostics provide the automatic detection of module faults. The TMR architecture of the
output module and the diagnostics performed ensure the validity of all critical circuits. Using the TMR
architecture provides a Fault Tolerant method to withstand the first fault occurrence on the module and
continue normal output controls without interruption in the system or process. Faults are reported to
the user through the Healthy status indicators on the front panel of the module and through the
information reported to the TMR Processor. Under normal operations all three Healthy indicators are
green. When a fault occurs, one of the Healthy indicators will be flashing red. This indicates that the
module should be replaced.
Module replacement activities depend on the type of spare module configuration chosen when the system was
configured and installed. The module may be configured with a Dedicated Standby Slot or with a SmartSlot for a
spare replacement module.
From the IMB to the field connector, the I/O module contains extensive fault detection and integrity
testing. As an output device, most testing is performed in a non-interfering mode. Data input from the
IMB is stored in redundant error-correcting RAM on each slice portion of the HIU. Received data is
voted on by each slice. All data transmissions include a confirmation response from the receiver.
Periodically, the TMR Processor commands the onboard DSPs to perform a Safety Layer Test. The
SLT results in the DSP verifying with the TMR Processor its ability to process data with integrity. In
addition, the DSP uses Cyclical Redundancy Checks (CRC) to verify the variables and configuration
stored in Flash memory.