add or remove alarms on additional pumps, if any, otherwise, the button will
not be visible. The alarm output screens for pumps #2-4 are the same as pump
#1.

Secured Screen

This screen is only accessible with "Admin" or "Supervisor" access. The Clear
Alarm History
button is used to clear all of the alarms from the alarm history.

PowerFlex 4 series VFD set up (must have firmware version 6.0 or higher)

If PowerFlex 4 VFD’s are being used, the following parameters need to be set
on each VFD.

1. P36 (start source) = 5 (comm port). If using backup control P36=2 (2

wire).

2. P38 (speed reference) =5 (comm port).If using backup control P38=0

(drive pot).

3. If using backup control, A51 (digital In 1) =6 (comm port). Otherwise

A51=0.

4. PowerFlex 4/40 - A103 (comm data rate) = 5 (38.4k), PowerFlex 400 -

C103 (comm data rate) = 5 (38.4k)

5. PowerFlex 4/40 - A104 (comm node address) = 1-4, PowerFlex 400 -

C104 (comm node address) = 1-4

6. The PLC is programed to control PowerFlex 4 VFD’s at node address

1-4. If pump #1 is a PowerFlex 4 drive, it must be set to node “1”. If
pump #2 is a PowerFlex 4 drive, it must be set to node “2”, and so on
with the remaining pumps.