Flash Updates
C-1
A
PPENDIX
C
Flash Updates
Appendix C provides information on updating peripheral product
firmware.
C.1
Preparing for a Flash Update
A Flash update should be preformed when updated peripheral
product firmware is available.
Please take the following precautions to ensure a successful Flash
update:
• Obtain the new firmware version from Rockwell Automation. Save
it to the hard drive of the computer. Do not attempt to perform a
Flash procedure from a floppy disk or a network.
• Read all instructions supplied with the new firmware file.
• Use a computer running terminal emulation software that
supports Xmodem transfers (for example, HyperTerminal).
• Record parameter values in the device that will be Flashed.
Updates may reset parameters to their default settings.
• Ensure that the host product (MD60 or MD65 AC drive) is
stopped.
• Close all programs except the terminal emulation program that
you are using to Flash the Serial Converter.
• Disable the screen saver and antivirus programs so that they do
not start during the Flash process.
• If you are using a laptop computer, turn off the FIFO buffers in
HyperTerminal. In HyperTerminal, select File > Properties to
display the Properties dialog box. Click Configure, and then click
Advanced. Ensure that a check mark does not appear next to
Use FIFO buffers.