Serial Converter Parameters
B-3
This parameter is a command. The value will be set to Ready after a
Reset Module command or Set Defaults command has been
performed.
Resets the DF1 statistical parameters (numbers 07 to15) to 0 if set
to Clear Counts. This parameter is a command. The value will be
set to Ready after a Clear Counts command has been performed.
Number of DF1 packets sent by the Serial Converter. The value of
this parameter is normally approximately equal to the value of DF1
Packets Rcvd (08).
05
Reset Module
Range:
0 = Ready (No action)
1 = Reset Module (Resets the Serial Converter)
2 = Set Defaults (Restores the Serial Converter
to its factory-default settings)
Default:
0
Type:
Read/Write
Reset Required: No
!
ATTENTION: If the Serial Converter is transmitting
control I/O to the product (indicated by a steady
green diamond LED on the Serial Converter), the
product may fault when you remove or reset the
Serial Converter. Determine how your product will
respond before removing or resetting a connected
Serial Converter. Failure to observe this precaution
could result in bodily injury and/or damage to
equipment.
06
Clear DF1 Counts
Range:
0 = Ready (No action)
1 = Clear Counts
Default:
0 = Ready (No action)
Type:
Read/Write
Reset Required No
07
DF1 Packets Sent
Range:
0 to 4294967295
Default:
0
Type:
Read Only