beautypg.com

Rockwell Automation 1786-series ControlNet Coax Media Planning and Installation Guide User Manual

Page 28

background image

28

Publication CNET-IN002B-EN-P - June 2010

Chapter 2 Plan a ControlNet Coax Media System

Install Repeaters in a Combination of Series and Parallel

You can install repeaters in a combination of

series

and

parallel

connections to

form a link. Follow the guidelines listed for each type. For mixed topologies
(series and parallel), you can verify the maximum number of repeaters and
media by using RSNetWorx for ControlNet software.

The illustration shows an example of repeaters installed in series and
in parallel.

TIP

If your network is configured using repeaters in combination of
series and parallel, you need to count the taps and repeaters in
all segments.

IMPORTANT

If the network is redundant, each redundant network (A or B)
must have the same number of repeaters configured in the
same topology.

1786-RPA

1786-RPA

1786-RPA

1786-RPA

1786-RPCD

1786-RPCD

CH1

CH2

1786-RPCD

CH1

CH2

1786-RPCD

CH1

CH2

1786-RPCD

CH1

CH2

1786-RPA

1786-RPCD

CH1

CH2

1786-RPA

1786-RPCD

CH1

CH2

31509-M

Segment 7

Repeaters D, E, and F
are installed in parallel

Repeater D

Repeater E

Repeater F

Segment 1

Segment 2

Segment 3

Node 1

Node 2

Node 3

Segment 4

Segment 5

Segment 6

Repeaters A, B, and C are installed in series and
connected to the repeaters in parallel via segment 7

Node 4

Node 5

Node 6

Repeater A

Repeater B

Repeater C