beautypg.com

Restart procedure, 1 introduction, 2 power up procedure – Rockwell Automation 8000 Series TMR System  User Manual

Page 32: 3 8000 series cabinet, Module ejector levers and key, Tmr interface module replacement

background image

OPERATOR AND MAINTENANCE MANUAL

D o c N o 5 5 2 8 6 4

P a g e 2 2 o f 2 2

I s s u e 0 2 J u n e 2 0 0 4

8. RESTART PROCEDURE

8.1 INTRODUCTION

The procedure described below is necessary to restore the 8000 Series System to
full operation after a total loss of power including the loss of the incoming power
supplies. The sequence is based on the assumption that the incoming power
supplies have been restored after all the MCBs, contactors and isolators have been
opened. It is assumed that all the application software and system INI configuration
have been installed.

Note

(1) Before powering the system, ascertain the status of the plant and ensure

that no danger to personnel or damage to the plant will occur.

(2) It is recommended that the 8000 Series System should always be

powered up in this sequence from cold.

(3) The last item to be powered–up will be the two Controller chassis.

8.2 POWER UP PROCEDURE

(1) Ensure that any system or devices attached to the system are ready for the

powering sequence.

(2) Open the 8000 Series System Cabinet doors to gain access to the incoming

240VAC system isolators. Ensure that the supply voltage is a nominal
240VAC. Close the 240VAC isolators.

(3) Close all the 240VAC MCBs. Check that both the 8000 Series System Power

Supply chassis are powered.

(4) Power the fan trays and roof fan assemblies, by closing the pairs of 24VDC

MCBs located on the MCB Panel.

(5) Power the main 8000 Series System I/O Chassis by closing the associated

pairs of 24VDC MCBs located on the MCB Panel.

(6) Finally, power the 8000 Series System Controller Chassis by closing the

associated pairs of 24VDC MCBs located on the MCB Panel.

(7) Close the 240VAC Utilities Assembly MCBs mounted in the 8000 Series

System Cabinets.

(8) Ensure that the 8000 Series System Engineering Workstation has power (if

applicable).

8.3 8000 SERIES CABINET

(1) Press the reset pushbutton on the 8000 Series System Processor Modules.

(2) Ensure that all 8000 Series System Modules are healthy, and that the 8000

Series System PLC is communicating.

(3) Close and lock all doors.