4 8000 series i/o modules, Module status indicators – Rockwell Automation 8000 Series TMR System User Manual
Page 22
OPERATOR AND MAINTENANCE MANUAL
D o c N o 5 5 2 8 6 4
P a g e 1 2 o f 2 2
I s s u e 0 2 J u n e 2 0 0 4
4.4 8000 SERIES I/O MODULES
LED INDICATION
Healthy
Module health.
Off
= No power applied to the module.
Amber
= Slice is in the start-up state (momentary after
installation or power-up).
Green
= healthy.
Flashing red
= fault present on the associated slice but the
slice is still operational.
Red (momentary) = On installation – power applied to the
associated slice.
Red
= The associated slice is in the fatal state. A
critical fault has been detected and the slice
has been disabled.
Active
Off
= module is not in the Active state.
Green
= module is in the Active state.
Flashing red
= Module is in the shutdown state if the
Standby LED is off.
Flashing red
= Module is in the fatal state if the Standby
LED is also flashing red.
Standby
Off
= module is not in the Standby state.
Green
= module is in the Standby state.
Flashing red
= module is in fatal state. The Active LED will
also be flashing red..
Educated
Off
= module is not educated.
Green
= module is educated.
Flashing green
= module is recognised by the processor but
education is not complete.
Channel LED
(40-off)
Off
= open field switch (contact).
Green
= closed field switch (contact).
Flashing red
= associated channel faulty.
Flashing green
= associated channel input voltage out of
range, i.e. either below the lowest trip
threshold or above the highest.
Note: The LEDs indicating channel status may be configured to suit user
requirements by implementing the procedure for configuring a System.INI file
detailed in PD-8010.