I/O Power Supply Assembly (T8060,T8062)
2
Industrial Control Services
Structure
The power supply assembly consists of a power supply chassis containing
up to six power supply modules. The chassis may be configured to
distribute power in various combinations. For example, a chassis containing
six power supply modules may be set up with three modules providing
triplicated power for Regent+Plus I/O assemblies and three modules
providing field power in a N+1 configuration.
Power Supply Chassis
The power supply chassis houses a maximum of six power supply modules.
It may be mounted in a 19-inch rack or flush mounted on a panel. Table 1
identifies the available types of chassis.
Table 1. Chassis Types
Catalog No.
Chassis Unit
Input Power Voltage
Configuratio
n
T8200
I/O Power Supply Chassis 110-240 VAC, 50/60 Hz
Straight Bussed
T8201
I/O Power Supply Chassis 110-240 VAC, 50/60 Hz
Cross Bussed
T8202
I/O Power Supply Chassis
24 VDC
Power Supply Modules
The power supply assembly modules are single (if redundant inputs are not
required) and dual input, hot swap, user-replaceable AC and DC units.
Table 2 identifies the available types of modules.
Table 2. Module Types
Catalog
No.
Input
Type
Input Power
Voltage
Output Power
Voltage
T8220
Dual
110-240 VAC
15 VDC
T8222
Dual
24 VDC
15 VDC
T8223
Single
110-240 VAC
24 VDC
T8224
Single
110-240 VAC
15 VDC
T8225
Dual
110-240 VAC
24 VDC
T8226
Dual
24 VDC
24 VDC