I/O Power Supply Assembly (T8060,T8062)


P D - 6 0 5 0 M a r - 0 6

15

Specifications (Continued)

Operating Humidity

0 to 95% relative humidity, non-
condensing

Vibration

10 to 55 Hz:

±0.15mm

Shock

Operating:

15 g, ½ sine wave, 11 msec

Electromagnetic Interference

IEC 801 Part 2 - Electrostatic

Discharges

IEC 801 Part 3 - Radiated

Electromagnetic Fields

IEC 801 Part 4 - Transients

and Bursts

IEC 801 Part 5 - Surge

Immunity

ANSI/IEEE C37.90 - Surge

Withstand Capability

Level 3: Contact discharge of

6 kV

Level 3: 10 V/M, 27 MHz -

500 MHz

Level 4: 2 kV, 2.5 kHz for

t = 60 sec

Level 3: 2 kV

2.5 kV damped 1 MHz sine
wave

4 kV bi-directional impulse, 10
nsec rise time, fast transient

Safety

Certified to DIN V VDE 0801
for Risk Class 5. Also designed
to meet UL 508 and CSA 22.2,
No. 142-M1981

Module Dimensions

Height:

Width:

Depth:

10.47" ( 266 mm)

2.38" ( 61 mm)

12.5" (318 mm)

Chassis Dimensions

Height:

Width:

Depth:

10.47" ( 266 mm)

19" ( 483 mm)

13.5" (343 mm)

This manual is related to the following products: