Entity Parameters
Entity parameters are a system of quantified safe levels for voltage,
current, inductance, and capacitance used when connecting multiple
devices.
The following table details the entity parameters that must be taken
into account when designing a FLEX Ex system.
In the table above, power sources are devices such as outputs or
inputs, and power receivers are devices such as transmitters.
In use, the sum of all the input internal capacitance (C
i
) or internal
inductance (L
i
) in a control loop cannot exceed the allowed
capacitance (C
o
) or allowed inductance (L
o
).
Also, the open-circuit voltage (U
o
) or short circuit current (I
o
) cannot
exceed the maximum input voltage (U
i
) or maximum input current
(I
i
).
Table 6.B
Entity Terms:
Applied to:
CENELEC
FM/CSA
Maximum output (open-circuit) voltage
Power sources
U
o
V
oc
Maximum output (short circuit) current
Power sources
I
o
I
sc
Maximum allowed capacitance
Power sources
C
o
C
a
Maximum allowed inductance
Power sources
L
o
L
a
Maximum input voltage
Power receivers
U
i
V
max
Maximum input current
Power receivers
I
i
I
max
Maximum internal capacitance
Power receivers
C
i
C
I
Maximum internal inductance
Power receivers
L
i
L
I