4-14 Input, Status, Output and Configuration Files for the Thermocouple/RTD/mV Module on the ControlNet Network
Chapter Summary
In this chapter you learned about input, output and configuration files
for the analog I/O modules on ControlNet. Move to Chapter 5 to learn
how to calibrate your module
Configuration
Word 1 cont.
Bits 14-15
(16-17)
Input Type Select
Bit
15
14
Input type selection for channels 4-7
0
0
Thermocouple
0
1
RTD
1
0
Not used
1
1
Configuration
Word 2
00-15 (00-17)
RTD loop resistance offset select bits – used input type is set to RTD and sensor mode select is set to
2-wire with loop resistance compensation. Allows you to set the type of RTD loop resistance compensation
used for all RTDs or one of three fixed values for all channels. NOTE: Not applicable to 10
Ω
copper RTD,
which defaults to 0
Ω
.
Bit
01
00
RTD channel 0
Bit
03
02
RTD channel 1
Bit
05
04
RTD channel 2
Bit
07
06
RTD channel 3
Bit
09
08
RTD channel 4
Bit
11
10
RTD channel 5
Bit
13
12
RTD channel 6
Bit
15
14
RTD channel 7
0
0
Use channel loop compensation value stored during calibration procedure for
2-wire RTD (default = 0
Ω
)
0
1
5
Ω
1
0
10
Ω
1
1
15
Ω
Configuration
Word 3
00-07
Module command data bits – These bits are written to the module during calibration. They are used to
define offset, gain and general channel calibration.
08-14 (10-16)
Module command bits – These bits are written to the module during calibration. They are used to select
channel calibration action.
15 (17)
Reserved for factory use only.
Configuration
Word
Dec. Bits
(Octal Bits)
Description